Installation & Operation Manual
19
2
General
venting
(continued)
Outdoor venting
• In order to properly vent the appliance in an outdoor
configuration the optional outdoor vent kit must be used
(see Table 2E).
•
Vent materials for outdoor venting are to be field supplied.
•
The vent must terminate at least 36 inches above the top of
the
unit.
•
All vent materials must be supported as recommended by
the vent manufacturer.
•
The terminations in Table 2F must be used.
Model Outdoor
Kit
2500 - 3000
100274941
3500
100274942
4000
100274943
5000
100274944
Table 2E Outdoor Vent Kits
Before installing a venting system, follow
all requirements found in the General
Venting section of this manual.
Outdoor vent / air inlet location
Keep venting areas free of obstructions. Keep area clean and free
of combustible and fl ammable materials. Maintain minimum
clearances to combustibles as stated in this manual.
Do not install outdoor models directly on the ground. You must
install the outdoor unit on a concrete, brick, block, or pressure-
treated wood platform.
NOTICE
Only install outdoor models outdoors,
and only use the vent caps specified in
this manual. Personal injury or product
damage may result if any other cap is used,
or if an outdoor model is used indoors.
Properly install all covers, doors, and jacket
panels to ensure proper operation and
prevent a hazardous condition.
Units are self-venting and can be used outdoors when installed
with the optional outdoor kit. All vent materials must be fi eld
supplied and supported per the vent manufacturer’s instructions.
Combustion air supply must be free of contaminants (see the
Combustion and Ventilation Air Requirements section of this
manual). To prevent recirculation of the fl ue products into the
combustion air inlet, follow all instructions in this section.
WARNING
Model
ProTech
Z-Flex
Heat Fab
Metal Fab
Security Chimney
Adapter
Flue
Adapter
Flue
Adapter
Flue
Adapter
Flue
Adapter
Flue
2500
810003982
FSCN0907
2SVDSA09
2SVSXITC09
9901MAD
CCA09EX07
8FCGLCA
9FCSEC-C60
SS9CRESTU
SS9ECU
3000 - 3500
810003984
FSCN1008
2SVDSA10
2SVSXITC10
91001MAD
CCA10EX08
10FCGLCA
10FCSEC-C60
SS9CRESTU
SS10ECU
4000
810003987
FSCN1210
2SVDSA12
2SVSXITC12
91201MAD
CCA12EX10
12FCGLCA
12FCSEC-C60
SS12CRESTU
SS12ECU
5000
810003990
FSCN1412
2SVDSA14
2SVSXITC14
91401MAD
CCA14EX12
14FCGLCA
14FCSEC-C60
SS14CRESTU
SS14ECU
Table 2F_Approved Adapters and Flue Terminations