User’s Information Manual

2  

Maintenance schedule

5

Service technician

(see the Knight Wall Mount Service Manual)

General: 

 

• Reported problems

 

• Inspect interior; clean and vacuum if 

  

necessary

 

• Clean condensate trap and fill with fresh 

  

water

 

 Check for leaks (water, gas, flue, 

  

condensate)

 

• Verify flue and air lines in good condition 

 

  and sealed tight

 

• Check system water pressure/system 

  

piping/expansion 

tank

 

• Check control settings

 

• Ignition and flame sense electrodes 

   (sand off any deposits; clean and 
  

reposition)

 

• Wiring and connections

 

 

 

 Perform start-up checkout and 

    performance verification per Section 
         10 in the Knight Wall Mount Installation 
         and Operation Manual.

 

• Flame inspection (stable, uniform)

 

• Flame signal (at least 4 mA)

 

 Clean the heat exchanger if flue 

 

 temperature is more than 54°F above 

 

  return water temperature.

If combustion or performance 
indicate need:

 

 • Clean heat exchanger

 

 •

 Remove and clean burner using 

 

   compressed air only 

 

 • Clean the blower wheel 

Owner maintenance

(see pages 6 - 8 for detailed instructions)

Daily

 

• Check boiler area

 

    Check pressure/temperature 

  

 

gauge

Monthly

 

• Check vent piping

 

• Check air piping

 

• Check air and vent termination 

  

screens

 

• Check relief valve

 

• Check condensate drain system

 

    Check air vents 

Periodically

 

• Test low water cutoff (if used)

 

• Reset button (low water cutoff)

Every

6 months

 

• Check boiler piping (gas and 

 

  water) for leaks

 

• Operate relief valve

End

of season 

months

 

•  Shut boiler down (unless boiler 

 

   used for domestic hot water)

 WARNING

Follow the maintenance procedures given throughout this manual.  Failure to perform the service and 
maintenance or follow the directions in this manual could result in damage to the boiler or system, 
resulting in severe personal injury, death, or substantial property damage.

ANNUAL START-UP

Содержание Knight 211

Страница 1: ...likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a near...

Страница 2: ...lt in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage Contents HAZARD DEFINITION...

Страница 3: ...ical supply to the circulator Instead shut off the gas supply at a location external to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance...

Страница 4: ...hments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishmen...

Страница 5: ...54 F above return water temperature If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheel Owner maintenance see page...

Страница 6: ...ntaminate the boiler intake air will cause acidic condensate in the boiler This will cause significant damage to the boiler if allowed to continue Read the list of potential materials listed in Table...

Страница 7: ...nstalled in the unit open this is needed as a vacuum break The blocked drain switch will shut the boiler down before any condensate can flow out of the tee Use materials approved by the authority havi...

Страница 8: ...t the lever completely the valve or discharge line may be blocked Immediately shut down the boiler following the operating instructions on page 9 of this manual Call your qualified service technician...

Страница 9: ...User s Information Manual 9 3 Operating instructions o C...

Страница 10: ...s the RIGHT SELECT HOME key again to store the new settings and return to the Status Screen Please note that the brackets denote screen status NOTICE Adjusting parameters CAUTION Before changing param...

Страница 11: ...disappear Press the HOME key to save these skipped triggers If you selected any currently active trigger s the current Night Setback will be cancelled There are three 3 individual user set points for...

Страница 12: ...for an additional 10 seconds to clear the combustion chamber and vent system of residual flue products SHUTDOWN The unit has been placed in the OFF position The controlled temperature has exceeded it...

Страница 13: ...The status of the DHW pump output BMS VOLTAGE The voltage received from a BMS system BLR PUMP OUTPUT The speed signal sent to a variable speed boiler pump in percent SYS PUMP INPUT The speed signal r...

Страница 14: ...g indicated by the cursor Pressing the NAVIGATION dial will display the Set Points Screen Turning the NAVIGATION dial will move the cursor up or down Turning the NAVIGATION dial will increase or decre...

Страница 15: ...15 Notes User s Information Manual...

Страница 16: ...odel numbers for the Knight Wall Mount upgrade Revision B ECO C07072 reflects the change in design of the manual air vent the update of FIG 2 3 on page 8 and the reorganization of the information on p...

Отзывы: