User’s Information Manual

2  

Maintenance schedule

6

Maintenance procedures

Boiler must be serviced and maintained

 WARNING

The boiler must be inspected and started 
annually at the beginning of the heating 
season by a qualified service technician.  
In addition, the maintenance and care 
of the boiler designated on page 5 of this 
manual and explained on pages 6 through 
8 must be performed to assure maximum 
boiler efficiency and reliability.  Failure to 
service and maintain the boiler and system 
could result in equipment failure, causing 
possible severe personal injury, death, or 
substantial property damage.

 NOTICE

The following information provides 
detailed instructions for completing 
the maintenance items listed in the 
maintenance schedule on page 5.  In 
addition to this maintenance, the boiler 
must be serviced and started up at the 
beginning of each heating season by a 
qualified service technician.

Check boiler area

 WARNING

To prevent potential of severe personal 
injury, death, or substantial property 
damage, eliminate all materials discussed 
below from the boiler vicinity and the 
vicinity of the boiler combustion air inlet.  
If contaminants are found:

Remove products immediately from the 
area.  If they have been there for an 
extended period, call a qualified service 
technician to inspect the boiler for possible 
damage from acid corrosion.

If products cannot be removed, 
immediately call a qualified service 
technician to re-pipe vent and air piping 
and locate vent termination/air intake 
away from contaminated areas.

1.  Combustible/flammable materials -- Do not store 
 

combustible materials, gasoline or any other flammable 

 

vapors or liquids near the boiler.  Remove immediately if 

 found.

2.  Air contaminants -- Products containing chlorine or 
 

fluorine, if allowed to contaminate the boiler intake air, 

 

will cause acidic condensate in the boiler.  This will cause 

 

significant damage to the boiler if allowed to continue.   

 

Read the list of potential materials listed in Table 1A on 

 

page 4 of this manual.  If any of these products are in the 

 

room from which the boiler takes its combustion air, they 

 

must be removed immediately or the boiler combustion 

 

air (and vent termination) must be relocated to another 

 area.

Check pressure/temperature gauge

1.  Make sure the pressure reading on the boiler pressure/ 
 

temperature gauge does not exceed 24 psi.  Higher 

 

pressure may indicate a problem with the expansion 

 tank.

2.  Contact a qualified service technician if problem persists.

Check vent piping

1.  Visually inspect the flue gas vent piping for any signs of 
 

blockage, leakage, or deterioration of the piping.  Notify 

 

your qualified service technician at once if you find any 

 problems.

 WARNING

Failure to inspect the vent system as noted 
above and have it repaired by a qualified 
service technician can result in vent system 
failure, causing severe personal injury or 
death.

Check air piping

1.  Visually inspect the air inlet termination to be sure it is 
 

unobstructed.  Inspect the entire length of air piping to 

 

ensure piping is intact and all joints are properly sealed.

2.  Call your qualified service technician if you notice any 
 problems.

Check relief valve

1.  Inspect the boiler relief valve and the relief valve 
 

discharge pipe for signs of weeping or leakage.

2.  If the relief valve often weeps, the expansion tank may 
 

not be working properly.  Immediately contact your 

 

qualified service technician to inspect the boiler and 

 system.

Check condensate drain system

1.  Inspect the condensate drain line, condensate PVC 
 

fittings and condensate trap.

Fill condensate trap with water

1.  Remove the bezel on the front of the unit.

2.  Remove the PVC cap retaining screw from the PVC cap 

(FIG. 2-1).

3.  Remove the 2" PVC cap with the switch located at the top 
 

of the trap (FIG. 2-1).

Содержание Knight 211

Страница 1: ...likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a near...

Страница 2: ...lt in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage Contents HAZARD DEFINITION...

Страница 3: ...ical supply to the circulator Instead shut off the gas supply at a location external to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance...

Страница 4: ...hments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishmen...

Страница 5: ...54 F above return water temperature If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheel Owner maintenance see page...

Страница 6: ...ntaminate the boiler intake air will cause acidic condensate in the boiler This will cause significant damage to the boiler if allowed to continue Read the list of potential materials listed in Table...

Страница 7: ...nstalled in the unit open this is needed as a vacuum break The blocked drain switch will shut the boiler down before any condensate can flow out of the tee Use materials approved by the authority havi...

Страница 8: ...t the lever completely the valve or discharge line may be blocked Immediately shut down the boiler following the operating instructions on page 9 of this manual Call your qualified service technician...

Страница 9: ...User s Information Manual 9 3 Operating instructions o C...

Страница 10: ...s the RIGHT SELECT HOME key again to store the new settings and return to the Status Screen Please note that the brackets denote screen status NOTICE Adjusting parameters CAUTION Before changing param...

Страница 11: ...disappear Press the HOME key to save these skipped triggers If you selected any currently active trigger s the current Night Setback will be cancelled There are three 3 individual user set points for...

Страница 12: ...for an additional 10 seconds to clear the combustion chamber and vent system of residual flue products SHUTDOWN The unit has been placed in the OFF position The controlled temperature has exceeded it...

Страница 13: ...The status of the DHW pump output BMS VOLTAGE The voltage received from a BMS system BLR PUMP OUTPUT The speed signal sent to a variable speed boiler pump in percent SYS PUMP INPUT The speed signal r...

Страница 14: ...g indicated by the cursor Pressing the NAVIGATION dial will display the Set Points Screen Turning the NAVIGATION dial will move the cursor up or down Turning the NAVIGATION dial will increase or decre...

Страница 15: ...15 Notes User s Information Manual...

Страница 16: ...odel numbers for the Knight Wall Mount upgrade Revision B ECO C07072 reflects the change in design of the manual air vent the update of FIG 2 3 on page 8 and the reorganization of the information on p...

Отзывы: