Impinger II – Installation & Operation Manual
6
UTILITY SPECIFICATIONS REQUIRED – ELECTRIC
*Model
Energy
Power
Voltage
Current
Phase
Hz
Recommended
Electrical Specification
1130-xxx-U-Kxxx
Electric
10kW
120/208V
48 Amps
1
60 Hz
4 Wires, 2 Pole + N + G
1131-xxx-U-Kxxx
Electric
10kW
120/240V
42 Amps
1
60 Hz
4 Wires, 2 Pole + N + G
1132-xxx-U-Kxxx
Electric
10kW
208V
28 Amps
3
60 Hz
4 Wires, 3 Pole + G
1133-xxx-U-Kxxx
Electric
10kW
240V
25 Amps
3
60 Hz
4 Wires, 3 Pole + G
1134-xxx-N-Kxxx
Electric
10kW
380/220V
15 Amps
3
50 Hz
5 Wires, 3 Pole + N + G
1134-xxx-N-Kxxx
Electric
10kW
380/220V
15 Amps
3
60 Hz
5 Wires, 3 Pole + N + G
1135-xxx-U-Kxxx
Electric
10kW
480V
25 Amps
3
60 Hz
4 Wires, 3 Pole + G
1151-xxx-U-Kxxx Electric 10kW
200V 29
Amps
3
50/60 Hz
4 Wires, 3 Pole + G
1161-xxx-U-Kxxx
Electric
10kW
240V
42 Amps
1
60 Hz
3 Wires, 2 Pole + G
1162-xxx-U-Kxxx
Electric
10kW
208V
28 Amps
3
60 Hz
4 Wires, 3 Pole + G
1164-xxx-U-Kxxx
Electric
10kW
400V
42 Amps
3
50 Hz
5 Wires, 3 Pole + N + G
* REFERENCE MODEL NUMBER KEY
UTILITY SPECIFICATIONS REQUIRED – GAS
Model
Energy
Power
Voltage
Current
Phase
Hz
Recommended
Electrical Specification
Gas
1116-xxx-U-Kxxx
Nat. Gas
40,000 BTU
120 VAC
7 Amps
1
60 Hz
3 Wires, 1 Pole + N + G
40,000 BTU at 7 inches,
H
2
O column**
1117-xxx-U-Kxxx
L.P. Gas
40,000 BTU
120 VAC
7 Amps
1
60 Hz
3 Wires, 1 Pole + N + G
40,000 BTU at 11 inches,
H
2
O column**
1154-xxx-U-Kxxx Nat.
Gas H
s
13 KW
230 VAC
2 Amps
1
50 Hz
3 Wires, 1 Pole + N + G
H
s
13 KW/HR at 1.7 kPa,
H
2
O column**
1155-xxx-U-Kxxx L.P.
Gas H
s
13 KW
230 VAC
2 Amps
1
50 Hz
3 Wires, 1 Pole + N + G
H
s
13 KW/HR at 2.73
kPa, H
2
O column**
1178-xxx-U-Kxxx
Nat. Gas
40,000 BTU
120 VAC
7 Amps
1
60 Hz
3 Wires, 1 Pole + N + G
40,000 BTU at 7 inches,
H
2
O column**
GAS PRESSURE CONVERSION CHART
Inches of
Water Column
KPa m-Bar
Millimeters of
Water Column
3.5 0.87
8.70
88.9
4.5 1.12
11.2
114.3
7 1.74
17.40
177.8
10 2.48
24.87
254.0
10.5 2.61
26.11
266.7
11 2.73
27.36
279.4
14 3.48
34.81
355.6
14.5 3.61
36.05
368.3
** NOTE: For proper operation, the gas valve requires a nominal inlet pressure of 7
inches of H
2
O for natural gas and 11 inches of H
2
O column for L.P. gas. A minimum
inlet pressure of 1.0 inch of H
2
O column above the manifold setting (NAT. manifold
3.5” H
2
O, L.P. manifold 10” H
2
O) must be maintained with no pressure drop from the
no load to full load condition. The maximum inlet pressure must be maintained at or
below ½ PSIG (14.5 inches H
2
O column). Refer to the chart on the left for pressure
conversions.
Electrical Supply for Australia:
Single Phase: 240 VAC, 50 Hz / 20 Amp; one neutral & one earth/ground.
Three Phase: 240/415 VAC / 20 Amp; three active, one neutral & one earth/ground.
All ovens require separate service and dedicated neutral.
NOTE: Do not install the (these) oven(s) in any area with an ambient temperature in
excess of 95°F / 35° C. Doing so will cause damage to the unit.