35
Alarm Output
Each fast dome has 1 alarm output. A dip switch can program the alarm output for NO (normally
open) or NC (normally close), that can activate the linked devices.
When alarm triggers, disable alarm as follows:
Push the joystick up, down, left, right or adjust the lens to disable the alarm.
Push
of the keyboard.
Recall preset position.
Push
of the keyboard to start Auto Pan mode.
Alarm Release Setting
1
2
ALARM
RESET
1
2
3
4
AUTO
PAN
The 6 alarm inputs of each fast dome are corresponding with the first 6 preset positions. When
an alarm signal is triggered, the dome will go to the relevant position at 360 /sec. Make sure
the first 6 preset positions are set to desired alarm areas.
Alarm input can be set to NC (normally close) or NO (normally open) depends on alarm detector.
Alarm Input 1 will send the dome to Preset Position 1
Alarm Input 2 will send the dome to Preset Position 2
Alarm Input 3 will send the dome to Preset Position 3
Alarm Input 4 will send the dome to Preset Position 4
Alarm Input 5 will send the dome to Preset Position 5
Alarm Input 6 will send the dome to Preset Position 6
。
Relationship Between Alarm Inputs and First 6 Presets
Alarm Management