4.2 AC power supply (-PM- order code)
AC power supply technical specifications
Input voltage:
Power consumption:
Fuse protection:
115Vac ... 230Vac (60/50Hz)
approx. 5 VA (unloaded)
external fuse T 0.1 A
The unit with -PM- order code also accepts AC power supply from 115 V to 230
V through terminal blocks 24 and 25. The power consumption depends on the
level of the supply voltage (approx. 5 VA) and the additional current required by
the Auxiliary Voltage output (3 – GND + 4 – Aux. Out, see the “4.3 Auxiliary
voltage output” section below).
Devices with -PM- order code can also be supplied with a DC voltage between
18 V and 30 V through terminals 1 and 2, see the previous “4.1 DC power
supply” section.
4.3 Auxiliary voltage output
Auxiliary voltage output technical specifications
DC version:
AC version:
24Vdc (approx. 1 V lower than the power supply
voltage), max. 250 mA or 5Vdc (±15%), max. 250
mA
24Vdc (±15%) (max. 150 mA up to 45°C / 80 mA
when more than 45°C) or 5Vdc (±15%), max.
250 mA
Terminal blocks 3 and 4 provide an auxiliary output useful for supplying sensors
and encoders.
The 24Vdc output voltage depends on the power supply, see the table above.
The unit allows the auxiliary voltage output to be set to either 24 Vdc or 5 Vdc.
Refer to the
parameter in the “6.3 SSI properties menu” section
on page 41.