LD220
Baud rate
It sets the clock frequency of the SSI telegrams. For more information please
refer to the “6.3.1 Reading the SSI data” section on page 44.
0 2 MHZ
N.A.
1 1.5 MHZ
N.A.
2 1 MHZ
1 MHz clock frequency
3 500 KHZ
500 kHz clock frequency
4 250 KHZ
250 kHz clock frequency
5 100 KHZ
100 kHz clock frequency
N.A. = not available
High bit
This parameter sets the highest bit (MSB) that must be evaluated when the bit
blanking function is used. For more information please refer to the “6.3.2.6
Evaluation of the bit blanking” section on page 50.
If you want the full encoder range to be evaluated, it must be set to the total
number of encoder bits.
01
Minimum value
25
Default value
32
Maximum value
Low bit
This parameter sets the lowest bit (LSB) that must be evaluated when the bit
blanking function is used. For more information please refer to the “6.3.2.6
Evaluation of the bit blanking” section on page 50.
If you want the full encoder range to be evaluated, it must be set to “01”.
01
Minimum value
...
32
Maximum value
Direction
It allows to set the direction of the motion of the connected SSI encoder:
clockwise / counter-clockwise (or forward / backward). For more information
please refer to the “6.3.2.5 Checking the direction of rotation” section on page
49.
0 FORWARD
Clockwise / Forward direction
1 REVERSE
Counter-clockwise / Reverse direction
MAN LD220 E 1.4.odt
6 – Menus and parameters
42 of 100