Liebert NX 10kVA Скачать руководство пользователя страница 5

iii

5.2

Configuring Parallel System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  34

5.2.1

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  34

5.2.2

Conditions for Parallel System  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  34

5.2.3

Features of Parallel System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  34

5.2.4

Operating Principles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  35

5.2.5

Operation Modes Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  35

5.2.6

Intermodule Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.3

Installing Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.3.1

Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.3.2

Preliminary Checks  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.3.3

Protective Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.3.4

Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.3.5

Parallel Control Cables  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

5.4

Commissioning a Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  37

5.5

Parallel System Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  38

5.5.1

Emergency Power Off (EPO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  38

5.6

Battery Circuit Breaker Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  38

6.0

S

PECIFICATIONS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41

6.1

Conformity and Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  41

6.2

UPS Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  41

6.3

UPS Mechanical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  41

6.4

UPS Electrical Characteristics  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  42

6.4.1

Battery Manufacturers and Models  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

6.4.2

Input Rectifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  42

6.4.3

DC Intermediate Circuit  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  42

6.4.4

Inverter Output  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  43

6.4.5

Bypass Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  43

7.0

I

NSTALLATION

 D

RAWINGS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44

8.0

S

PECIFICATIONS

 

AND

 T

ECHNICAL

 D

ATA

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53

8.1

Lug Size and Torque Requirements  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  53

8.2

Cable Lengths: Floor to Connection Point Inside UPS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  57

FIGURES

Figure 1

Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Figure 2

Single module block diagram (dual input configuration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10

Figure 3

Input busbars  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11

Figure 4

Battery fuses and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11

Figure 5

Ground and neutral busbar connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12

Figure 6

Monitor board U2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14

Figure 7

Auxiliary terminal block detail  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14

Figure 8

Input dry contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15

Figure 9

Output dry contacts and EPO wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16

Figure 10 Narrow battery cabinet, 27 in. (690mm) - rear view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  22

Содержание NX 10kVA

Страница 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...

Страница 2: ...ctory authorized service For LGS to assist you promptly please have the following information available Tag Number___________________________________________________________________ Site ID___________...

Страница 3: ...5 Floor Installation 7 1 5 6 Cable Entry 7 1 5 7 Optional Cabinets 8 2 0 ELECTRICAL CONNECTIONS 9 2 1 Power Cabling 9 2 1 1 Cable Rating 9 2 1 2 UPS Input Configuration 10 2 1 3 Cabling Guidelines 10...

Страница 4: ...ENANCE BYPASS CABINET 27 4 1 Bypass Switch 27 4 2 UPS Mode 27 4 3 Bypass Mode 28 4 4 Maintenance Mode 28 4 5 Mounting the Cabinet 28 4 6 Cable Installation 28 4 6 1 Wiring Preparation 28 4 6 2 Power C...

Страница 5: ...41 6 3 UPS Mechanical Characteristics 41 6 4 UPS Electrical Characteristics 42 6 4 1 Battery Manufacturers and Models 42 6 4 2 Input Rectifier 42 6 4 3 DC Intermediate Circuit 42 6 4 4 Inverter Output...

Страница 6: ...onnection 51 Figure 31 Maintenance Bypass interconnection 52 TABLES Table 1 Input dry contacts at X3 15 Table 2 Maintenance bypass cabinet interface 15 Table 3 BCB box interface 16 Table 4 Output dry...

Страница 7: ...ive and sulfuric acid can cause severe burns When connected the nominal battery voltage is 324VDC and is potentially lethal In case of fire involving electrical equipment use only carbon dioxide fire...

Страница 8: ...lways check with an AC and DC voltmeter to ensure safety before making contact or using tools Even when the power is turned Off dangerously high electric charges may exist within the UPS All power and...

Страница 9: ...caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grou...

Страница 10: ...amine the UPS and battery equipment for transit damage both internally and externally Report any such damage to the shipper and to Liebert immediately 2 Check the nameplate inside the cabinet door to...

Страница 11: ...tion Temperature is a major factor in determining battery life and capacity Battery manufacturers recom mend an operating temperature of 77 F 25 C Ambient temperatures warmer than this reduce bat tery...

Страница 12: ...s and auxiliary equipment Enough space to service the UPS Air circulation sufficient to expel heat produced by UPS Protection against moisture and excessive humidity Protection against dust and other...

Страница 13: ...available For information see your local Lie bert representative If the equipment is to be placed on a raised floor it should be mounted on a pedestal that will support the equipment point loading Re...

Страница 14: ...inet ONLY after the units are connected and positioned Battery cabinets may be bolted to either side of the NX unless used in configurations that include a Maintenance Bypass Cabinet refer to 1 5 7 O...

Страница 15: ...d output cables must be sized for the nominal output current given in Table 20 with respect to the unit rating and the output AC voltage Battery cables Each UPS unit has its own internal batteries fac...

Страница 16: ...und cable connecting the UPS to the main ground system must follow the most direct route possible 3 Consider using paralleled smaller cables for heavy currents this can ease installation 4 When sizing...

Страница 17: ...mpartment The batteries are connected to fuses to protect the NX and connected equipment see Figure 4 Figure 4 Battery fuses and connections NOTE External battery connection access requires removal of...

Страница 18: ...and Table 11 for overload capacity High speed fuses and SCRs are used for internal battery circuit overcurrent protection When an external battery supply is used overcurrent protection for the battery...

Страница 19: ...5 N m M6 bolt 8 For Rectifier Input connect AC input supply cables between the power distribution panel and the UPS input circuit breaker A B C terminals 9 The bypass input neutral cable must be conn...

Страница 20: ...elay Emergency Power Off control EPO Environmental parameter input interface User communication for data setting and user background monitor Intellislot interface Modem interface Temperature detect in...

Страница 21: ...configured by configuration software before becoming active 2 When activated the charger current can be limited via software to a percentage of the full charger current 0 100 3 Activating this feature...

Страница 22: ...ive when BCB interface is connected N O NOTE All auxiliary cables of terminal must be double insulated Wire should be 16 20AWG stranded Table 4 Output dry contact relays Position Name Description J13...

Страница 23: ...se general conditions are met the UPS may be started 2 4 1 Startup Procedure To start the UPS from a fully powered down condition 1 Open the UPS door to gain access to the main power switches 2 Turn t...

Страница 24: ...nce bypass The bypass and load indicators turn on The design of the rotary switch ensures uninterrupted output 5 Turn the rotary switch to NORMAL then press the INVERTER ON control button for 2 second...

Страница 25: ...pplied by the manual Maintenance bypass 2 6 Powering Down the UPS To power down the UPS completely follow the procedures in 2 5 Switching the UPS from Nor mal to Maintenance Bypass To completely isola...

Страница 26: ...igned maxi mum ambient temperature not the UPS In the case of valve regulated batteries for example the ambient room temperature should be kept between 68 F and 86 F 20 30 C not between 32 F and 104 F...

Страница 27: ...ys work from the bottom shelf up to prevent raising the center of gravity which could cause a tip over hazard 3 6 2 Connecting the Batteries If the NX battery cabinets are installed on a raised floor...

Страница 28: ...mm rear view Figure 11 Wide battery cabinet 57 in 1488mm front view BCB plate and BCB Battery trays Top cable entry Bottom cable entry Batteries Battery tray Anderson connectors Top cable entry BCB pl...

Страница 29: ...Battery Installation 23 Figure 12 Battery cabinet details Insulated post for cabling Tray handle Removable retainer...

Страница 30: ...cabinet relative to the UPS An A or 1 designation means the cabinet is adjacent to the UPS Cabinet B will be adjacent to cabinet A If the system includes a matching maintenance bypass cabinet MBC the...

Страница 31: ...t below the power connections All cabinets in the UPS system must be connected to the user s ground connection 5 Connect the system battery cables from the UPS battery output terminals N to battery ca...

Страница 32: ...ontact your local Liebert sales representative about this option Install battery racks cabinets and batteries in accordance with the manufacturer s instructions Verify that the battery area has adequa...

Страница 33: ...ernal Maintenance Bypass Cabinet typical configuration 4 1 Bypass Switch The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass source 4 2 UPS Mode While the Ma...

Страница 34: ...ed by the UPS The Bypass Switch is in the MAINTENANCE position for this mode 4 5 Mounting the Cabinet This Maintenance Bypass Cabinet may be mounted to the left of the UPS or installed as stand alone...

Страница 35: ...cables between the Maintenance Bypass Cabinet UPS Input Busbars A B C N terminals and UPS input busbars A B C N terminals and tighten the connections to 44 lb in 5 N m M6 bolt 8 Connect the system in...

Страница 36: ...be inserted from either the UPS side or from the MBS side whichever is more convenient NOTE UPS wiring must be completed before the cabinets are bolted together Dry contact for X3 Place cabinets so m...

Страница 37: ...SW to the Normal position on the Maintenance Bypass Cabinet The UPS will go to bypass mode 2 Press the Inverter On button on the UPS and allow the UPS to go to normal mode 3 The connected equipment i...

Страница 38: ...ansformer from 480VAC to 208VAC is determined by dividing 480 by 208 which equals 2 31 3 Using configuration software enable the output transformer configuration 4 Calculate the input to output voltag...

Страница 39: ...bypass source is the same for both systems 5 1 2 DBS Cable and Settings For Paradigm to Paradigm dual bus configuration with the help of only one optional DBS cable the built in DBS will operate norm...

Страница 40: ...inputs and outputs must be correct and the same The parallel logic cable and load sharing cable must be connected in a ring correctly See Figure 20 5 2 3 Features of Parallel System The hardware and f...

Страница 41: ...s within the synchronous range the inverter will be synchronized with the bypass Other wise the system will operate at nominal frequency Battery Mode Operation The batteries of all UPS modules power t...

Страница 42: ...for Parallel System 5 3 3 Protective Devices Refer to the instructions supplied in the Liebert NX installation manual SL 25215 5 3 4 Power Cables Wiring of power cables is similar to that of single mo...

Страница 43: ...el system should be set as Parallel configuration UPS ID No Each UPS module should have a unique identification number in the parallel sys tem Parallel system requisite UPS units Set the minimum numbe...

Страница 44: ...vailable for use in installations where the battery is not installed in the battery cabinet in which case the appropriate battery box is fitted as close as possible to the battery and connected to the...

Страница 45: ...breaker boxes are of the same size for the 10 kVA to 30 kVA UPS but switch capacity are different The information shown in Figure 22 applies to both sizes The BCB box contains a battery isolating cir...

Страница 46: ...92mm TYP 25 HDWR REMOVEABLE COVER CONDUIT ENTRY TOP BOTTOM 3 TB1 CUSTOMER GROUND 25 STUD FOR 6GA 2 0 WIRE O 50 12 7mm X6 FROM CUSTOMER S BATTERY SYSTEM FIELD INSTALLED FIELD SUPPLIED CONNECT TO UPS MO...

Страница 47: ...ics Rated Power 10 30kVA Operating Temperature UPS 32 F to 104 F 0 C to 40 C Optimal Operating Temperature Battery 68 F to 86 F 20 C to 30 C Relative Humidity 0 to 95 non condensing Acoustical Noise d...

Страница 48: ...nt Nominal A 28 42 56 83 Notes 1 Overload capacity of input current 100 Imax I 125 Imax 125 Imax I 150 Imax I 150 10 min 1 min Limits input current immediately Table 12 DC intermediate circuit Rated P...

Страница 49: ...ng PF Lagging Leading 0 5 0 6 0 7 0 8 0 9 1 0 0 9 0 8 0 7 0 6 0 5 K 200V 1 00 1 00 1 00 1 00 0 88 0 80 0 75 0 73 0 72 0 71 0 71 K 208V 1 00 1 00 1 00 1 00 0 88 0 80 0 75 0 73 0 72 0 71 0 71 Table 15 B...

Страница 50: ...loor stand Note If a floor stand is used the weight of the unit must be supported under all casters 10 Each mounting location is supported by two 10 GA 135 galvanized steel The threaded 12mm insert is...

Страница 51: ...igure 24 Dimensions continued top and bottom views Rearstabilizing foot optional Air Exhaust Power Cable Entry Area Top and Bottom Air Intake 10mm dia threaded mounting holes 4 typ See Notes 9 and 10...

Страница 52: ...sitions on control wiring may vary depending on which options are included on your unit 3 Refer to 3 0 Battery Installation for battery installation details 4 All wiring must be installed in accordanc...

Страница 53: ...run in separate conduit Output and input cables must be run in separate conduit 4 Aluminum and copper clad aluminum cables are not recommended 5 All wiring is to be in accordance with national and lo...

Страница 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...

Страница 55: ...tery connections TOP LAYER MIDDLE LAYER BOTTOM LAYER W500 18pcs W501 3pcs W502 to W503 W503 to W502 W504 to W505 W506 to W507 W510 to W511 CON4 Fuse 5 Fuse 4 W505 to W504 W508 to W509 W511 to W510 W50...

Страница 56: ...s 50 Figure 29 Electrical connections MONITOR BOARD A B C N TO CRITICAL LOAD 200 208V A B C N INPUT SUPPLY 200 208V SWITCH TO CUSTOMERS SAFETY EARTH EARTH POWER CABLES BATT N UPS BATTERY BCB INPUT MBC...

Страница 57: ...rs and protective plates 59 Battery Cabinet Front View without doors and protective plates Connection Detail Breaker Detail Breaker Detail Positive Midpoint N Negative Positive Midpoint N Negative A B...

Страница 58: ...und J Monitoring terminal block UPS terminal block Bypass contacts NOTES 1 All Liebert supplied cable must be repositioned prior to and while the cabinets are being placed in their final installed loc...

Страница 59: ...Wire Size or Range Lb in N m 6 4 100 11 3 1 125 14 1 0 2 0 150 17 3 0 200 MCM 200 23 250 400 MCM 250 28 500 700 MCM 300 34 Circuit Breakers With Compression Lugs For Power Wiring Current Rating Lb in...

Страница 60: ...mended Lug Lug T B One Hole 54000 Lug T B One Hole REDDY 10 24 9 31 37 40 6M 1 4 54130 62204 15 37 3 47 56 60 6M 1 4 54106 62204 20 49 8 62 75 80 6M 1 4 54107 62204 30 74 7 93 112 125 6M 1 4 54152 622...

Страница 61: ...70 90 220 52 70 020 D M 480 31 40 208 56 70 020 D M 600 25 40 208 56 70 020 D M 208 72 90 208 56 70 020 D M 220 68 90 208 56 70 020 E N 480 32 40 480 24 30 020 E N 600 26 40 600 19 30 020 E N 220 70 9...

Страница 62: ...4 15 208 60 6M 1 4 54106 62204 10 600 15 6M 1 4 NA 62204 10 480 20 6M 1 4 NA 62204 10 220 40 6M 1 4 54130 62204 10 208 40 6M 1 4 54130 62204 Output Unit Rating Nominal System Output Voltage OCP Device...

Страница 63: ...nce Bypass Cabinet Style lb kg A B C D E L J K M N 10kVA 408 185 545 247 675 306 602 273 732 332 670 304 403 183 540 245 597 271 728 330 15kVA 408 185 567 257 728 330 659 299 822 373 723 328 403 183 5...

Страница 64: ...Specifications and Technical Data 58 NOTES...

Страница 65: ...Specifications and Technical Data 59...

Страница 66: ...Specifications and Technical Data 60...

Страница 67: ......

Страница 68: ...ms all liability for damages resulting from use of this information or for any errors or omissions 2004 Liebert Corporation All rights reserved throughout the world Specifications subject to change wi...

Отзывы: