Options
35
Figure 19 1+1 system block diagram
5.2.4 Operating Principles
Redundancy Paralleling
The redundancy parallel system can noticeably improve system reliability. In normal condition, nei-
ther UPS module works at full load. That means that even if the load is increased, the system will not
transfer to bypass. And when a UPS module shuts down due to any failure, the remaining UPS mod-
ule can still power and protect the load. When redundancy is lost due to module failure or load
increase, the parallel system will trigger an alarm.
5.2.5 Operation Modes Summary
The parallel system also has operation modes such as normal, battery, bypass and maintenance
bypass. All UPS modules in the 1+1 parallel system operate in coordination.
•
Normal Mode Operation
The load is powered by the inverters of all the UPS modules in the system. If the frequency of
bypass is within the synchronous range, the inverter will be synchronized with the bypass. Other-
wise, the system will operate at nominal frequency.
•
Battery Mode Operation
The batteries of all UPS modules power the load through their inverters. The system operates at
nominal frequency.
•
Bypass Mode Operation
The condition to transfer to bypass mode is essentially the same as that of single module system.
The bypass of all the UPS modules powers the load.
•
Maintenance Bypass Mode Operation
The sequence to transfer to maintenance bypass mode is the same as for transferring a single-
module system. The maintenance bypass switches should be switched on as synchronously as pos-
sible. Thus the system can be repaired without interrupting the power supply to critical load.
RECTIFER
INVERTER
STATIC
QUPS
Q1EXT
CB1
SW1-C
SW1-D
SWITCH
N
INPUT MAINS
UPS1
BATTERY 1
SUPPLY A B C
FUSE
SW1-A
A B C
A B C
SWITCH
STATIC
INVERTER
Q2EXT
SW1-A
BATTERY 2
FUSE
SW1-D
SW1-C
RECTIFER
UPS2
CB1
SUPPLY A B C
INPUT MAINS
N
QBYP
DISTRIBUTION PANEL
TO LOAD
CHARGER
CHARGER
SUPPLIED BY OTHERS
Содержание NX 10kVA
Страница 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...
Страница 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...
Страница 64: ...Specifications and Technical Data 58 NOTES...
Страница 65: ...Specifications and Technical Data 59...
Страница 66: ...Specifications and Technical Data 60...
Страница 67: ......