Electrical Connections
16
2.3.3 BCB Box Interface
J10 is the BCB box interface.
2.3.4 Output Dry Contacts
There are three output dry contact relays at the X1 slot (see
and
).
Figure 9
Output dry contacts and EPO wiring
Table 3
BCB box interface
Position
Name
Description
J10.1
DRV
BCB Driver Signal - Output (N.O.)
J10.2
FB
BCB Contact State - Input (N.O.)
J10.3
GND
Power Ground
J10.4
OL
BCB On-Line - Input - This pin will become active when
BCB interface is connected. (N.O.)
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 16-20AWG stranded.
Table 4
Output dry contact relays
Position
Name
Description
J13.2
Gen_O
Generator Start Relay (N.O.)
J13.3
Gen_S
Generator Start Relay Center
J13.4
Gen_C
Generator Start Relay (N.C.)
J21.2
BPS_O
Bypass Mode Relay (N.O.)
J21.3
BPS_S
Bypass Mode Relay Center
J21.4
BPS_C
Bypass Mode Relay (N.C.)
J25.2
ACF_O
Main Input Fault Relay (N.O.)
J25.3
ACF_S
Main Input Fault Relay Center
J25.4
ACF_C
Main Input Fault Relay (N.C.)
NOTE
All auxiliary cables of terminal must be double insulated. Wire should be 16-20AWG stranded.
Содержание NX 10kVA
Страница 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...
Страница 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...
Страница 64: ...Specifications and Technical Data 58 NOTES...
Страница 65: ...Specifications and Technical Data 59...
Страница 66: ...Specifications and Technical Data 60...
Страница 67: ......