5

4.2 --- First start---up

(or after a long stop)

Operate as follows:

1)

At least 8 hours before the start---up, power the crank-

case heaters (if any, see point 4) by setting the main iso-

lator switch ON. Make sure the auxiliary circuit has been

powered and check the operation (a fault due to an in-

correct procedure will invalidate the compressor guar-

antee).

2) Open the valves of the refrigeration circuit that had been

closed before the initial check.

3) Check the machinery supplying the thermal load connected

with the unit and start the system pump(s).

4) MAKE SURE THE COMPRESSOR OIL HAS BEEN HEATED

FOR AT LEAST 8 HOURS; start the unit only then. In the

units not equipped with crankcase heaters (Chillers for sum-

mer operation only, without modulating fan speed control),

the start must be carried out in the warm season only (exter-

nal T > 15

û

C), and thus oil pre---heating is not necessary.

5) Make sure the fans rotate in the correct direction (anticlock-

wise): check the electrical connections, if necessary.

6) Make sure the pumps rotate in the correct direction.

7)

During the unit start---up an inlet water temperature

higher than 20

û

C is allowed. Under standard operating

conditions check that the limits indicated in paragraph

2.1 are not exceeded.

8) Check the correct operation of the control and safety de-

vices.

9) Check the outlet temperature of the chilled water (check if

the set---point set on the controller is reached).

10) Check the compressor oil level.

11) With the compressor at full load, check there are no

bubbles visible in the frefrigerant sight glass. If there are any,

charge the unit according to par. 5.

4.3 --- Starting and stopping

ALWAYS ENSURE THAT THE COMPRESSOR OIL HAS BEEN

PREHEATED.

FOR BRIEF STOPPAGES MAINTAIN THE SUPPLY TO THE

CRANKCASE HEATER (IF ANY).

S

Start the unit setting the Microprocessor switch

ON.

S

Stop the unit setting the Microprocessor switch

OFF

.

S

In case of long stops, turn the machine off using the Micro-

processor switch OFF.

In this case the compressor crankcase heaters (if any) re-

main powered.

S

For seasonal shutdown of the unit operate the main switch

located on the main electrical power supply. This will discon-

nect the compressor crankcase heaters.

4.4 --- Chillers serving special plants

The units are capable of cooling a water---glycol mixture to tem-

peratures close to 0

û

C without the need for significant modifica-

tions. In the case of modification, the set values of the safety and

control components must also be changed. This can be carried

out in the factory (at the time of testing) or at the time of installa-

tion, only by qualified and authorised personnel.

4.5 --- Freecooling

The “freecooling” is a system of pre---cooling and/or cooling the

water/glycol mixture using ambient air when the latter isat a tem-

perature below the return mixture temperature. If the outside

temperature is sufficiently low to dissipate the entire heat load,

the refrigeration compressors automatically switch off, and the

mixture’s temperature is controlled by the fan speed adjust-

ment.

If the mixture temperature is too high for freecooling, the com-

pressors will operate as long as necessary to ensure the correct

water/glycol mixture temperature.

4.6 --- Microprocessor control

Consult the ”Microface and Hiromatic” Service Manual.

5 --- Refrigerant and Oil Charge

All work on pipes or components of the refrigerating circuit un-

der pressure must be exclusively carried out by qualified staff,

competent in such works.

5.1 --- Refrigerant charge

WHILST REPAIRING THE REFRIGERATING CIRCUIT RE-

COVER ALL THE REFRIGERANT IN A CONTAINER: DO NOT

ALLOW IT TO ESCAPE. NEVER USE THE COMPRESSOR

FOR THE SYSTEM VACUUM (THIS INVALIDATES THE

WARRANTY).

S

The unit is delivered charged according to the Tab. 7.

Warning for the refrigerant charge:

S

Ensure there are no refrigerant leaks.

S

Check the refrigerant type in the refrigeration circuit: a unit

originally charged by the manufacturer with R407C cannot

be charged with R22 and vice versa; possibly apply to the

Technical Support Department.

S

Charge with the compressor in operation, connecting the

cylinder with the charge connector after the thermostatic ex-

pansion valve.

Flush the connection pipe between the cylinder and the

charging point; tighten the seal joint and then start charging

the unit. It is imperative that the cylinder is weighed both be-

fore and after the operation.

S

For the units with R407C the refrigerant charge must be

made exclusively with liquid refrigerant.

S

Charge the unit until the bubbles in the sight glass have dis-

appeared and the working conditions of the entire refrigera-

tion circuit have returned to normal (sub---cooling and su-

perheating within the limits indicated below).

S

Measure the superheating as follows:

1) Detect the temperature on the suction line, close to the

bulb of the thermostatic expansion valve, using a contact

thermometer.

2) Connect a pressure gauge (by max. a 30---cm pipe) with

the Schraeder connection and read the corresponding

saturated evaporating temperature.

3) The superheating is the difference between the two

readings.

4) For the units with R407C refer to the pressure gauge

scale indicated with the initials D.P. (Dew Point)

S

Verify that the superheating is 5

û

C --- 8

û

C.

S

Measure the sub---cooling as follows:

1) Detect the temperature on the liquid line using a contact

thermometer.

2) Connect a pressure gauge (by max. a 30---cm pipe) with

the Schraeder connection on the liquid line and read the

corresponding saturated condensing temperature.

3) The sub---cooling is the difference between the tworead-

ings.

4) For the units with R407C refer to the pressure gauge

scale indicated with the initials B.P. (Bubble Point)

S

Verify that at the condenser outlet, sub---cooling is 3

û

C ---

5

û

C.

IT IS IMPORTANT TO CARRY OUT CHARGING CORRECTLY.

An excess of refrigerant causes an increase in sub---cooling and

consequent operating difficulties in the hot season; a shortage

of charge generates an increase in superheating and possible

compressor stoppages. Whenever work is carried out on the

unit, ensure afterwards that the working conditions are correct,

checking sub---cooling and superheating.

Содержание MATRIX S 004-016

Страница 1: ...SERVICE MANUAL English Cod 272491 Rev 25 05 2005 Issued by T D Service HIGH PERFORMANCE AIR COOLED CHILLER S 004 016...

Страница 2: ......

Страница 3: ...read the identification labels affixed to the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user should al ways consul...

Страница 4: ...nsion valve The hydraulic circuit is made up of hydraulic lines both in steel and flexible EPDM rubber connected by fittings and threaded joints a flow switch optional and in the freecooling versions...

Страница 5: ...t the inlets of the pump and water chiller Can be supplied as an optional accessory Not fitted 8 Install at the highest points in the circuit apparatus which allows the bleeding of air and possibly th...

Страница 6: ...ing a diameter of at least that of the valve outlet without burdening the valve body Convey the discharge to areas where the jet cannot harm people and the surrounding environment Fig a Ideal chilled...

Страница 7: ...ors are equipped with anelectronic protectionde vice blocking their start if the phase sequence is not correct or stopping their operationif athermal relayintervenes Thisdevice is essential for the in...

Страница 8: ...ure s temperature is controlled by the fan speed adjust ment If the mixture temperature is too high for freecooling the com pressors will operate as long as necessary to ensure the correct water glyco...

Страница 9: ...with R407C R22 standard factory setting STOP 26 bar START 20 bar DIFF 6 bar fixed reset The settings for the safety valves installed on the machine are indicated below MODELS SETTINGS SAFETY VALVE 004...

Страница 10: ...ating between 5 C 8 C S Check that the oil level indicated by the compressor sight glass is higher than the min value CHILLED WATER CIRCUIT S Ensure that there are no water leaks S Bleed any air out o...

Страница 11: ...r control to disable the heat recovery protecting the system from any possible malfunctioning Fig e Recommended hydraulic circuit Heat recovery users Heat recovery exchanger 8 4 Hydraulic circuit acce...

Страница 12: ...20 Model 004 204 006 206 007 207 008 011 014 016 Heating capacity kW 10 8 14 8 18 2 21 6 29 6 36 4 44 3 Water flow l s 0 516 0 707 0 870 1 032 1 414 1 739 2 117 Water pressure drop kPa 8 11 14 8 11 14...

Страница 13: ...current kW A A 0 95 2 2 2 4 SHC std head pressure pump model Opt Std head pressure pump mot nom power Std head pressure pump mot max power Std head pressure pump max current SHC high head pressure pum...

Страница 14: ...ad pressure pump model Opt High head pressure pump motor power High head pressure pump max current kW kW A kW A 12 136 1 10 1 44 2 67 32 160 30 3 0 6 50 20 128 1 50 1 92 3 90 32 160 30 3 0 6 50 12 136...

Страница 15: ...ure switch Barg Barg Barg 26 0 28 0 29 0 2 8 1 With nominal air flow water flow outlet at 7 C full load SBH R 407C Size 004 006 007 204 206 207 008 011 014 016 Working Range Max outdoor air temperatur...

Страница 16: ...charge each circuit kg 7 8 12 2 15 3 5 0 6 7 8 5 8 7 12 8 16 2 18 3 Oil charge each circuit lt 6 20 8 00 3 25 3 30 6 20 8 00 Models CLH 004 006 007 204 206 207 008 011 014 016 Refrigerant charge each...

Страница 17: ...65 70 Pump weight kg 12 7 13 8 15 4 42 0 2 pole pump set standard head pressure data refers to each pump Models 004 006 007 204 206 207 008 011 014 016 SBH 30 glycol water mixture flow m3 h 7 90 10 86...

Страница 18: ...ea Extraordinary maintenance area 1000 1000 1000 1000 AIR AIR Notes Minimum distance between 2 units from condensing coil side 2m Do not obstruct the air exiting the fans for a minimum distance of 2 5...

Страница 19: ...it pins as shown above A The capacity of the lifting gear must be adequate to lift the load in question Check the weight of the unit the capacity of the lifting gear and ropes and the condition and su...

Страница 20: ...unit with a speed suitable for the load to be moved so as not to damage the structure G G Xg Yg A1 A2 STRAIGHT SHACKLE 14 UNI 1947 A TYPE OPTIONAL LIFTING SYSTEM WITH STRAIGHT SHACKLE N B LIFT IN THE...

Страница 21: ...7 0 60 1 52 0 60 CLH 004 0 79 0 54 0 88 0 55 CLH 006 0 78 0 52 0 86 0 53 CLH 007 1 15 0 54 1 29 0 55 CLH 204 0 76 0 60 Not available CLH 206 0 77 0 60 Not available CLH 207 1 12 0 60 Not available CLH...

Страница 22: ...7 0 60 1 60 0 60 SLH 004 0 83 0 55 0 91 0 55 SLH 006 0 82 0 53 0 89 0 54 SLH 007 1 21 0 54 1 33 0 55 SLH 204 0 80 0 60 Not available SLH 206 0 82 0 60 Not available SLH 207 1 18 0 60 Not available SLH...

Страница 23: ...4 206 207 008 011 014 016 161 181 187 206 217 229 245 305 314 260 260 114 127 135 95 103 108 115 123 129 138 114 127 135 95 195 234 240 206 217 229 245 305 314 260 260 114 127 135 95 124 140 147 123 1...

Страница 24: ...237 250 258 215 CLH 004 006 007 215 240 182 174 206 216 174 245 287 213 203 235 258 203 204 206 207 Not available Not available Not available 008 011 014 016 275 339 258 279 258 279 238 257 215 215 2...

Страница 25: ...11 014 016 174 197 201 219 232 242 261 325 332 287 287 145 165 175 137 125 135 143 145 158 169 145 165 175 137 206 248 251 219 232 242 261 325 332 287 287 145 165 175 137 148 170 179 145 158 169 145 1...

Страница 26: ...268 288 298 257 SLH 004 006 007 227 253 196 199 229 245 199 256 299 225 229 259 289 229 204 206 207 Not available Not available Not available 008 011 014 016 290 357 285 306 285 306 269 297 257 257 2...

Страница 27: ...nfiguration Support kit code Single support code Kit support pieces CBH 204 206 207 004 006 007 CLH 204 206 004 006 CQH 204 004 SBH 204 206 207 004 006 007 SLH 204 206 004 006 SQH 204 004 485620 4 CBH...

Страница 28: ...GAS MALE ON 204 206 207 MODELS TANK VERSION WITH WITHOUT PUMP IS NOT AVAILABLE 204 206 207 204 206 207 HEAT RECOVERY WATER CONNECTION OPTIONAL 016 016 LATERAL VIEW ONLY FOR CQH 016 SBH 007 AND SBH 01...

Страница 29: ...ion 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater Std with pressure transducer High pressure manometer Opt Low pressure manometer Opt Safe...

Страница 30: ...11 4 11 4 H 2 2 2 21 2 21 2 21 2 21 2 Refrigerant components Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heat...

Страница 31: ...Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater High pressure manometer Opt Low pressure manometer Opt Saf...

Страница 32: ...QH SBH SLH SQH 204 206 207 008 011 014 016 G 2 2 2 21 2 21 2 21 2 21 2 H 2 2 2 21 2 21 2 21 2 21 2 Refrigerant components Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor...

Страница 33: ...ents Item Description Item Description 1 2 3 4 5 6 7 8 9 10 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve E...

Страница 34: ...7 8 9 10 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve Drain valve 11 12...

Страница 35: ...3 4 5 6 7 8 9 10 11 12 13 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve D...

Страница 36: ...freeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve Drain valve Control temperature sensor Antifreeze tem...

Страница 37: ...d Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est em...

Страница 38: ...of EMERSON Tel 39 049 9719111 Telefax 39 049 5841257 Internet www liebert hiross com Printed in Italy by Liebert HIROSS S p A Issued by T D Service Since the Liebert HIROSS Company has a policy of co...

Отзывы: