2

Note:

Avoid positioning in areas with possible reverberation of the

sound waves, which can adversely effect the noise levels.

2.3 --- Transport

S

Handle the unit by lifting it with a crane from above;

S

The lifting holes are positioned in the frame’s base (when lift-

ing, use spreader bars to protect the sides, see Fig. 2 and

Fig. 3).

Note:

Place the lifting tubes in the holes in the base indicated by ”LIFT

HERE”. Lock the ends of the tubes with the locking pins and

splits pins as shown in Fig. 2. As an alternative, shackles/hooks

(optional) fastened at the base ends can be used as a lifting sy-

stem: in this case the lifting point must be on the vertical line

passing through the machine’s centre of gravity (as indicated in

Fig. 3) to prevent any load imbalance.

The capacity of the lifting gear must be adequate to lift the load

in question. Check the weight of the units, the capacity of the lift-

ing gear and ropes and the condition and suitability of the afore-

mentioned equipment.

2.4 --- Foundations

S

The unit must be placed on a level surface which will support

its weight.

S

If necessary, position the unit on suitable anti---vibration sup-

ports that can be supplied as an option (in rubber or spring---

type). Refer to the manual ”Installation of the spring anti---

vibration supports” for their correct positioning.

S

When positioned, level the unit.

Note:

For weight distribution see Fig. 4 and Fig. 5.
Note:

The weights and their distribution refer to standard units without

options; if the pump assembly, or other options are installed on

the machine, add the weights of the installed accessories to

those of the standard units (see Tab. 8).

2.5 --- Service area

S

In order to allow free air flow and maintenance of the unit, a

minimum area must be left free of obstructions around the

unit (see Fig. 1).

S

The hot air expelled by the fans mustbe allowed to rise unim-

peded by obstacles for a minimum height of 2.5 m.

S

Avoid recirculation of hot air between the suction and dis-

charge, otherwise the unit performance may be impaired or

the standard operation can be interrupted.

3 --- Installation

3.1 --- Hydraulic connections

3.1.1 -- Hydraulic circuit construction (Fig. a)

The piping must be connected to the chiller. Construct a chilled

water circuit as described below, see Fig. a:

1) Place shut---off valves within the circuit to allow servicing;

2) Install a pump system suitable for the flow rate required at

a pressure head equal to the sum of all the pressure drops

(see project data).

Matrix S chillers can be equipped, upon request, with

pumps having performance as indicated in Tab. 8;

3) Install manometers at the chiller inlet/outlet;

4) Install thermometers at the chiller inlet/outlet;

5) Connect the pipes to the chiller by flexible joints to avoid

transmitting vibrations and to balance the thermal expan-

sion; proceed in the same way even if the pump set is out-

side the chiller;

6) It is useful to include a water pressure switch to give an early

warning of low water pressure;

7) Place a mesh filter at the inlets of the pump and water chiller

(Can be supplied as an optional accessory ---Not fitted);

8) Install, at the highest points in the circuit, apparatus which

allows the bleeding of air and possibly the filling of glycol;

9) Place a drain valve at the lowest point in the circuit and im-

mediately at the outlet of the water chiller;

10) Install a water filling set including the following:

a) filling water meter;
b) manometer;
c) non---return valve;
d) air separator;
e) removable supply tube,

which must be disconnected

after each charge/top---up;

11) For maximum protection ensure that all tubing exposed to

low outdoor temperatures is fitted with anti---freeze heaters

and insulated using closed cell synthetic rubber (elasto-

mer);

12) The circuit must include an expansion vessel (with safety

valve) of suitable capacity;

13) Connect the lines avoiding stresses on the machine inner

parts.

Note:

If the water chiller is complete with an expansion vessel (sup-

plied as an option), check if the capacity is enough, and install

a second vessel in the circuit, if required (see par. 8.4).

Follow the indications in Fig. c for the correct sizing.
Note:

The whole circuit must contain a water volume suitable for the

capacity of the installed chiller. Check if the inertial capacity giv-

en by the sum of the hydraulic volume inside the machine (in-

cluding the volume of the optional interna tank, if fitted) and the

system volume issufficient, or possibly installa tank in the circuit.

Follow the indications in Fig. b for the correct sizing.
Note:

The hydraulic circuit must ensure a constant water supply to the

evaporator in every operating condition. Otherwise, the com-

pressors may be damaged by repeated returnsof liquid refriger-

ant on their suction.
Note:

The water flow switch is a compulsory safety component that

must be installed and correctly wired to the Matrix S chillers,

otherwise the guarantee will be invalidated.

It is installed, as standard, on units with the optional on---board

pump set, and is available as a option for units without pumps

on board: in the latter case the flow switch, if not installed on the

machine, can be installed on the hydraulic circuit by the installer,

but it is compulsory that it is wired to the electric panel terminal

board, as indicated on the wiring diagram.

3.1.2 -- Addition of water and ethylene glycol

Very important:
Add water and ethylene glycol to the circuit with a % depending

on the minimum temperature of the outside air expected at the

installation site. Do not exceed the nominal operating pressure

of the circuit’s components.
Notes:

S

To avoid stratification run the circulation pump for at least 30

minutes after adding any glycol.

S

After adding water to the hydraulic circuit

always discon-

nect the water supply coming from the sanitary supply;

this avoids the danger of glycol entering the sanitary water

system.

S

After any topping---up of the water check the concentration

and add glycol if necessary.

3.1.3 -- Water--glycol mixture

Water---glycol mixtures are used as the thermal carrier fluid in

very cold climatesor with temperatures below zero degreescen-

tigrade. Determine the ethylene glycol % which must be added

to the water, with the assistance of Tab. a.

Содержание MATRIX S 004-016

Страница 1: ...SERVICE MANUAL English Cod 272491 Rev 25 05 2005 Issued by T D Service HIGH PERFORMANCE AIR COOLED CHILLER S 004 016...

Страница 2: ......

Страница 3: ...read the identification labels affixed to the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user should al ways consul...

Страница 4: ...nsion valve The hydraulic circuit is made up of hydraulic lines both in steel and flexible EPDM rubber connected by fittings and threaded joints a flow switch optional and in the freecooling versions...

Страница 5: ...t the inlets of the pump and water chiller Can be supplied as an optional accessory Not fitted 8 Install at the highest points in the circuit apparatus which allows the bleeding of air and possibly th...

Страница 6: ...ing a diameter of at least that of the valve outlet without burdening the valve body Convey the discharge to areas where the jet cannot harm people and the surrounding environment Fig a Ideal chilled...

Страница 7: ...ors are equipped with anelectronic protectionde vice blocking their start if the phase sequence is not correct or stopping their operationif athermal relayintervenes Thisdevice is essential for the in...

Страница 8: ...ure s temperature is controlled by the fan speed adjust ment If the mixture temperature is too high for freecooling the com pressors will operate as long as necessary to ensure the correct water glyco...

Страница 9: ...with R407C R22 standard factory setting STOP 26 bar START 20 bar DIFF 6 bar fixed reset The settings for the safety valves installed on the machine are indicated below MODELS SETTINGS SAFETY VALVE 004...

Страница 10: ...ating between 5 C 8 C S Check that the oil level indicated by the compressor sight glass is higher than the min value CHILLED WATER CIRCUIT S Ensure that there are no water leaks S Bleed any air out o...

Страница 11: ...r control to disable the heat recovery protecting the system from any possible malfunctioning Fig e Recommended hydraulic circuit Heat recovery users Heat recovery exchanger 8 4 Hydraulic circuit acce...

Страница 12: ...20 Model 004 204 006 206 007 207 008 011 014 016 Heating capacity kW 10 8 14 8 18 2 21 6 29 6 36 4 44 3 Water flow l s 0 516 0 707 0 870 1 032 1 414 1 739 2 117 Water pressure drop kPa 8 11 14 8 11 14...

Страница 13: ...current kW A A 0 95 2 2 2 4 SHC std head pressure pump model Opt Std head pressure pump mot nom power Std head pressure pump mot max power Std head pressure pump max current SHC high head pressure pum...

Страница 14: ...ad pressure pump model Opt High head pressure pump motor power High head pressure pump max current kW kW A kW A 12 136 1 10 1 44 2 67 32 160 30 3 0 6 50 20 128 1 50 1 92 3 90 32 160 30 3 0 6 50 12 136...

Страница 15: ...ure switch Barg Barg Barg 26 0 28 0 29 0 2 8 1 With nominal air flow water flow outlet at 7 C full load SBH R 407C Size 004 006 007 204 206 207 008 011 014 016 Working Range Max outdoor air temperatur...

Страница 16: ...charge each circuit kg 7 8 12 2 15 3 5 0 6 7 8 5 8 7 12 8 16 2 18 3 Oil charge each circuit lt 6 20 8 00 3 25 3 30 6 20 8 00 Models CLH 004 006 007 204 206 207 008 011 014 016 Refrigerant charge each...

Страница 17: ...65 70 Pump weight kg 12 7 13 8 15 4 42 0 2 pole pump set standard head pressure data refers to each pump Models 004 006 007 204 206 207 008 011 014 016 SBH 30 glycol water mixture flow m3 h 7 90 10 86...

Страница 18: ...ea Extraordinary maintenance area 1000 1000 1000 1000 AIR AIR Notes Minimum distance between 2 units from condensing coil side 2m Do not obstruct the air exiting the fans for a minimum distance of 2 5...

Страница 19: ...it pins as shown above A The capacity of the lifting gear must be adequate to lift the load in question Check the weight of the unit the capacity of the lifting gear and ropes and the condition and su...

Страница 20: ...unit with a speed suitable for the load to be moved so as not to damage the structure G G Xg Yg A1 A2 STRAIGHT SHACKLE 14 UNI 1947 A TYPE OPTIONAL LIFTING SYSTEM WITH STRAIGHT SHACKLE N B LIFT IN THE...

Страница 21: ...7 0 60 1 52 0 60 CLH 004 0 79 0 54 0 88 0 55 CLH 006 0 78 0 52 0 86 0 53 CLH 007 1 15 0 54 1 29 0 55 CLH 204 0 76 0 60 Not available CLH 206 0 77 0 60 Not available CLH 207 1 12 0 60 Not available CLH...

Страница 22: ...7 0 60 1 60 0 60 SLH 004 0 83 0 55 0 91 0 55 SLH 006 0 82 0 53 0 89 0 54 SLH 007 1 21 0 54 1 33 0 55 SLH 204 0 80 0 60 Not available SLH 206 0 82 0 60 Not available SLH 207 1 18 0 60 Not available SLH...

Страница 23: ...4 206 207 008 011 014 016 161 181 187 206 217 229 245 305 314 260 260 114 127 135 95 103 108 115 123 129 138 114 127 135 95 195 234 240 206 217 229 245 305 314 260 260 114 127 135 95 124 140 147 123 1...

Страница 24: ...237 250 258 215 CLH 004 006 007 215 240 182 174 206 216 174 245 287 213 203 235 258 203 204 206 207 Not available Not available Not available 008 011 014 016 275 339 258 279 258 279 238 257 215 215 2...

Страница 25: ...11 014 016 174 197 201 219 232 242 261 325 332 287 287 145 165 175 137 125 135 143 145 158 169 145 165 175 137 206 248 251 219 232 242 261 325 332 287 287 145 165 175 137 148 170 179 145 158 169 145 1...

Страница 26: ...268 288 298 257 SLH 004 006 007 227 253 196 199 229 245 199 256 299 225 229 259 289 229 204 206 207 Not available Not available Not available 008 011 014 016 290 357 285 306 285 306 269 297 257 257 2...

Страница 27: ...nfiguration Support kit code Single support code Kit support pieces CBH 204 206 207 004 006 007 CLH 204 206 004 006 CQH 204 004 SBH 204 206 207 004 006 007 SLH 204 206 004 006 SQH 204 004 485620 4 CBH...

Страница 28: ...GAS MALE ON 204 206 207 MODELS TANK VERSION WITH WITHOUT PUMP IS NOT AVAILABLE 204 206 207 204 206 207 HEAT RECOVERY WATER CONNECTION OPTIONAL 016 016 LATERAL VIEW ONLY FOR CQH 016 SBH 007 AND SBH 01...

Страница 29: ...ion 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater Std with pressure transducer High pressure manometer Opt Low pressure manometer Opt Safe...

Страница 30: ...11 4 11 4 H 2 2 2 21 2 21 2 21 2 21 2 Refrigerant components Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heat...

Страница 31: ...Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater High pressure manometer Opt Low pressure manometer Opt Saf...

Страница 32: ...QH SBH SLH SQH 204 206 207 008 011 014 016 G 2 2 2 21 2 21 2 21 2 21 2 H 2 2 2 21 2 21 2 21 2 21 2 Refrigerant components Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor...

Страница 33: ...ents Item Description Item Description 1 2 3 4 5 6 7 8 9 10 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve E...

Страница 34: ...7 8 9 10 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve Drain valve 11 12...

Страница 35: ...3 4 5 6 7 8 9 10 11 12 13 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve D...

Страница 36: ...freeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve Drain valve Control temperature sensor Antifreeze tem...

Страница 37: ...d Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est em...

Страница 38: ...of EMERSON Tel 39 049 9719111 Telefax 39 049 5841257 Internet www liebert hiross com Printed in Italy by Liebert HIROSS S p A Issued by T D Service Since the Liebert HIROSS Company has a policy of co...

Отзывы: