11
SBH -- R 407C
Size
004
006
007
204
206
207
008
011
014
016
Power supply
---
400 V / 3 Ph / 50 Hz
OA
(1)
FLA
LRA
Compressors power input
(1)
Compressors nominal current
(1)
Compressor max. current
A
A
A
kW
A
A
29
39
179
14.5
25
35
37
54
219
19.7
33
50
44
73
274
24.4
40
69
30
42
121
14.5
26
19
39
62
163
19.4
35
29
49
68
181
24.8
45
32
58
78
218
28.9
50
35
74
108
273
39.2
66
50
88
146
347
48.6
80
69
109
155
403
59.0
98
72
Fan power input
Fan nominal current
Fan max. current
kW
A
A
1.90
3.8
4.0
SHC std. head pressure pump model (Opt.)
FHE std. head pressure pump model (Opt.)
Std. head pressure pump mot. nom. power
Std. head pressure pump mot. max. power
Std. head pressure pump max. current
FHE high head pressure pump model (Opt.)
High head pressure pump motor power
High head pressure pump max. current
---
---
kW
kW
A
---
kW
A
12---136
---
1.10
1.44
2.67
32---160/30
3.0
6.50
20---128
---
1.50
1.92
3.90
32---160/30
3.0
6.50
12---136
---
1.10
1.44
2.67
32---160/30
3.0
6.50
20---128
---
1.50
1.92
3.90
32---160/30
3.0
6.50
20---134
---
1.85
2.45
4.61
40---160/40
4.0
8.50
---
40---160/40
4.0
4.0
8.50
40---200/75
7.5
15.50
Electrical cable section (min.)
mm
2
16
25
35
16
25
35
35
50
70
70
(1) Outdoor air temperature 35
û
C; 30% glycol water mixture; water inlet/outlet temperature 15/10
û
C
SLH -- R 407C
Size
004
006
007
204
206
207
008
011
014
016
Power supply
---
400 V / 3 Ph / 50 Hz
OA
(1)
FLA
LRA
Compressors power input
(1)
Compressors nominal current
(1)
Compressor max. current
A
A
A
kW
A
A
29
37
177
15.3
26
35
35
52
217
19.6
33
50
45
74
275
23.7
40
69
29
40
119
15.3
27
19
37
60
161
19.3
35
29
49
69
182
24.1
44
32
57
75
215
30.4
52
35
69
105
270
38.9
64
50
85
145
346
47.0
78
69
109
151
399
63.0
102
72
Fan power input
Fan nominal current
Fan max. current
kW
A
A
1.00
2.3
2.4
SHC std. head pressure pump model (Opt.)
FHE std. head pressure pump model (Opt.)
Std. head pressure pump mot. nom. power
Std. head pressure pump mot. max. power
Std. head pressure pump max. current
FHE high head pressure pump model (Opt.)
High head pressure pump motor power
High head pressure pump max. current
---
---
kW
kW
A
---
kW
A
12---136
---
1.10
1.44
2.67
32---160/30
3.0
6.50
20---128
---
1.50
1.92
3.90
32---160/30
3.0
6.50
12---136
---
1.10
1.44
2.67
32---160/30
3.0
6.50
20---128
---
1.50
1.92
3.90
32---160/30
3.0
6.50
20---134
---
1.85
2.45
4.61
40---160/40
4.0
8.50
---
40---160/40
4.0
4.0
8.50
40---200/75
7.5
15.50
Electrical cable section (min.)
mm
2
16
25
35
16
25
35
35
50
70
70
(1) Outdoor air temperature 35
û
C; 30% glycol water mixture; water inlet/outlet temperature 15/10
û
C
SQH -- R 407C
Size
004
006
007
204
206
207
008
011
014
016
Power supply
---
400 V / 3 Ph / 50 Hz
OA
(1)
FLA
LRA
Compressors power input
(1)
Compressors nominal current
(1)
Compressor max. current
A
A
A
kW
A
A
27
36
176
14.4
25
35
35
53
218
18.8
32
50
44
72
273
24.8
41
69
27
39
118
14.4
26
19
36
61
162
18.5
34
29
49
67
180
25.1
46
32
53
73
213
28.7
50
35
68
104
269
37.8
64
50
86
142
343
49.9
82
69
106
148
396
62.3
102
72
Fan power input
Fan nominal current
Fan max. current
kW
A
A
0.75
1.4
1.5
SHC std. head pressure pump model (Opt.)
FHE std. head pressure pump model (Opt.)
Std. head pressure pump mot. nom. power
Std. head pressure pump mot. max. power
Std. head pressure pump max. current
FHE high head pressure pump model (Opt.)
High head pressure pump motor power
High head pressure pump max. current
---
---
kW
kW
A
---
kW
A
12---136
---
1.10
1.44
2.67
32---160/30
3.0
6.50
20---128
---
1.50
1.92
3.90
32---160/30
3.0
6.50
12---136
---
1.10
1.44
2.67
32---160/30
3.0
6.50
20---128
---
1.50
1.92
3.90
32---160/30
3.0
6.50
20---134
---
1.85
2.45
4.61
40---160/40
4.0
8.50
---
40---160/40
4.0
4.0
8.50
40---200/75
7.5
15.50
Electrical cable section (min.)
mm
2
16
25
35
16
25
35
35
50
70
70
(1) Outdoor air temperature 35
û
C; 30% glycol water mixture; water inlet/outlet temperature 15/10
û
C
•
Nominal power supply = 400 V; 3 Ph; 50 Hz
•
Nominal power supply tolerance = 400 V ±10 %
•
Max. voltage unbalance = 3 %
•
The cables have to be sized in compliance with local standards and according to the type and characteristics of installation. Suggested cables section are re-
ferred to PVC insulation with a max. working temperature of 70
û
C and an ambient temperature of 30
û
C.
Содержание MATRIX S 004-016