7 --- Maintenance

The Maintenance Programme below must be carried out by a

qualified technician, preferably working under a maintenance

contract.
Before any intervention on the unit or accessing the inner com-

ponents (removing the outer panels), always ensure the ma-

chine is switched off. If the rear panels are removed (coil com-

partment) wait for the fan(s) to come to a complete stop before

accessing the compartment; if the front panelsare removed, pay

special attention when working near the compressor upper part

and the discharge line: they are very hot; possibly wait for them

to cool. Be very careful when operating close to the finned coils,

as the fins are very sharp. Do not remove the fan protection grille

before electrically isolating the whole machine. Do not insert

foreign matter through the fan protection grille. After the main-

tenance interventions, always close the unit with the suitable

panels, fastened by the tightening system.

7.1 --- Spare parts

The use of original spare parts is recommended.

When placing an order refer to the ”Component List” enclosed

with the machine and quote the unit model no. and serial no.

7.2 --- Dismantling the unit

The machine has been designed and built to ensure continuous

operation.

The working life of some of the main components, such as the

fans and the compressors, depends on the maintenance that

they receive.

If the unit has to be dismantled, the job must be done by skilled

refrigeration technicians.

The refrigerant and the lubricating oil in the circuit must be dis-

posed of in conformity with the laws in force in your country.

Maintenance programme -- Monthly check

FANS

S

Check that the fan motor rotates freely without any abnormal noise, and ensure that the

bearings are not running hot.

S

Also check the current absorption.

CONDENSER AND AIR FILTER

S

Check the conditions of the filters (if they are supplied); if necessary clean them (including

the electrical panel ventilation filter).

S

Check the condenser coils and clean if necessary with compressed air or soft brushes.

CONTROL

S

Check that the control equipment, LEDs and display are operating correctly.

ELECTRICAL CIRCUIT

S

Check the electrical supply on all phases.

S

Ensure that all electrical connections are tight.

REFRIGERATION CIRCUIT

S

Check the condensing and the evaporating pressures (to be done by a refrigeration techni-

cian).

S

Check the compressor’s current absorption, the delivery temperature and possible unusual

noises.

S

Check the refrigerant charge by means of the sight glass.

S

Check that the safety devices operate correctly.

S

Check the correct operation of the thermostatic valve (superheating between 5

û

C

---

8

û

C).

S

Check that the oil level indicated by the compressor sight glass is higher than the min. value.

CHILLED WATER CIRCUIT

S

Ensure that there are no water leaks.

S

Bleed any air out of the hydraulic circuit using the bleed valves.

S

Verify that the water flow rate is correct.

S

Check the inlet --- outlet liquid temperature and pressure.

S

Check the correct operation of the three---way valve (Versions with free---cooling only).

S

Check if the system is charged with the specified glycol percentage and that no ice has

formed in the hydraulic circuit.

S

Check the evaporator cleanliness.

8 --- Options and Accessories

8.1 --- Pump set

The centrifugal pump units are direct driven, with close---

coupled motors and a single shaft; the induction motor has 2

poles with IP 54 protection and class F insulation.
The materials used for the pump main components are:

S

Pump body in plastic material PA 6.6 (cast iron in all high

pressure freecooling versions and on model 016 in the Chil-

ler high head pressure version and Superchiller standard

head pressure version);

S

Impeller in in plastic material PPO (stainless steel in all high

pressure freecooling versions and on model 016 in the Chil-

ler high head pressure version and Superchiller standard

head pressure version);

S

Stainless steel shaft;

S

Graphite impregnated ceramic mechanical seal (EPDM in

all high pressure freecooling versions and on model 016 in

the Chiller high head pressure version and Superchiller

standard head pressure version), suitable for the use of mix-

tures containing ethylene glycol.

The pump units have been chosen and sized to operate within

specific limits, namely:

S

Water / ethylene glycol mixtures up to 65% / 35% by weight;

S

Temperatures of the standard pumped fluid not lower than

4

°

C.

The hydrauliccircuitincludes, for each pump, a suction shut---off

valve and a delivery check valve if two pumps are installed, or

suction and delivery shut---off valves if a single pump isinstalled.
In the electrical panel there are automatic circuit breakers for

each pump; the microprocessor control manages the operating

rotation between the two pumps and start---up of the stand---by

pump if the primary pump fails.
For the technical features of the pumps and the hydraulic sche-

matic see Tab. 8, Fig. 12, Fig. 13, Fig. 14 and Fig. 15.

8.2 --- Water chiller with partial heat

recovery (20%)

This option enables the recovery of up to20% of the heatnormal-

ly rejected by the condensers. The system does not require any

adjustment and is made up of plate heat exchangers installed

on each circuit before the condenser. The exchangers are pro-

tected by a suitable anti---frost heater that operates when the sy-

stem is stopped. It is recommended that a safety valve be

installed in the hydrauliccircuittoavoid hazardsdue tooverpres-

sures, if there is no water flow through the recuperator.

Содержание MATRIX S 004-016

Страница 1: ...SERVICE MANUAL English Cod 272491 Rev 25 05 2005 Issued by T D Service HIGH PERFORMANCE AIR COOLED CHILLER S 004 016...

Страница 2: ......

Страница 3: ...read the identification labels affixed to the outside and inside of the unit IMPORTANT This manual may be subject to modification for complete and up to date information the user should al ways consul...

Страница 4: ...nsion valve The hydraulic circuit is made up of hydraulic lines both in steel and flexible EPDM rubber connected by fittings and threaded joints a flow switch optional and in the freecooling versions...

Страница 5: ...t the inlets of the pump and water chiller Can be supplied as an optional accessory Not fitted 8 Install at the highest points in the circuit apparatus which allows the bleeding of air and possibly th...

Страница 6: ...ing a diameter of at least that of the valve outlet without burdening the valve body Convey the discharge to areas where the jet cannot harm people and the surrounding environment Fig a Ideal chilled...

Страница 7: ...ors are equipped with anelectronic protectionde vice blocking their start if the phase sequence is not correct or stopping their operationif athermal relayintervenes Thisdevice is essential for the in...

Страница 8: ...ure s temperature is controlled by the fan speed adjust ment If the mixture temperature is too high for freecooling the com pressors will operate as long as necessary to ensure the correct water glyco...

Страница 9: ...with R407C R22 standard factory setting STOP 26 bar START 20 bar DIFF 6 bar fixed reset The settings for the safety valves installed on the machine are indicated below MODELS SETTINGS SAFETY VALVE 004...

Страница 10: ...ating between 5 C 8 C S Check that the oil level indicated by the compressor sight glass is higher than the min value CHILLED WATER CIRCUIT S Ensure that there are no water leaks S Bleed any air out o...

Страница 11: ...r control to disable the heat recovery protecting the system from any possible malfunctioning Fig e Recommended hydraulic circuit Heat recovery users Heat recovery exchanger 8 4 Hydraulic circuit acce...

Страница 12: ...20 Model 004 204 006 206 007 207 008 011 014 016 Heating capacity kW 10 8 14 8 18 2 21 6 29 6 36 4 44 3 Water flow l s 0 516 0 707 0 870 1 032 1 414 1 739 2 117 Water pressure drop kPa 8 11 14 8 11 14...

Страница 13: ...current kW A A 0 95 2 2 2 4 SHC std head pressure pump model Opt Std head pressure pump mot nom power Std head pressure pump mot max power Std head pressure pump max current SHC high head pressure pum...

Страница 14: ...ad pressure pump model Opt High head pressure pump motor power High head pressure pump max current kW kW A kW A 12 136 1 10 1 44 2 67 32 160 30 3 0 6 50 20 128 1 50 1 92 3 90 32 160 30 3 0 6 50 12 136...

Страница 15: ...ure switch Barg Barg Barg 26 0 28 0 29 0 2 8 1 With nominal air flow water flow outlet at 7 C full load SBH R 407C Size 004 006 007 204 206 207 008 011 014 016 Working Range Max outdoor air temperatur...

Страница 16: ...charge each circuit kg 7 8 12 2 15 3 5 0 6 7 8 5 8 7 12 8 16 2 18 3 Oil charge each circuit lt 6 20 8 00 3 25 3 30 6 20 8 00 Models CLH 004 006 007 204 206 207 008 011 014 016 Refrigerant charge each...

Страница 17: ...65 70 Pump weight kg 12 7 13 8 15 4 42 0 2 pole pump set standard head pressure data refers to each pump Models 004 006 007 204 206 207 008 011 014 016 SBH 30 glycol water mixture flow m3 h 7 90 10 86...

Страница 18: ...ea Extraordinary maintenance area 1000 1000 1000 1000 AIR AIR Notes Minimum distance between 2 units from condensing coil side 2m Do not obstruct the air exiting the fans for a minimum distance of 2 5...

Страница 19: ...it pins as shown above A The capacity of the lifting gear must be adequate to lift the load in question Check the weight of the unit the capacity of the lifting gear and ropes and the condition and su...

Страница 20: ...unit with a speed suitable for the load to be moved so as not to damage the structure G G Xg Yg A1 A2 STRAIGHT SHACKLE 14 UNI 1947 A TYPE OPTIONAL LIFTING SYSTEM WITH STRAIGHT SHACKLE N B LIFT IN THE...

Страница 21: ...7 0 60 1 52 0 60 CLH 004 0 79 0 54 0 88 0 55 CLH 006 0 78 0 52 0 86 0 53 CLH 007 1 15 0 54 1 29 0 55 CLH 204 0 76 0 60 Not available CLH 206 0 77 0 60 Not available CLH 207 1 12 0 60 Not available CLH...

Страница 22: ...7 0 60 1 60 0 60 SLH 004 0 83 0 55 0 91 0 55 SLH 006 0 82 0 53 0 89 0 54 SLH 007 1 21 0 54 1 33 0 55 SLH 204 0 80 0 60 Not available SLH 206 0 82 0 60 Not available SLH 207 1 18 0 60 Not available SLH...

Страница 23: ...4 206 207 008 011 014 016 161 181 187 206 217 229 245 305 314 260 260 114 127 135 95 103 108 115 123 129 138 114 127 135 95 195 234 240 206 217 229 245 305 314 260 260 114 127 135 95 124 140 147 123 1...

Страница 24: ...237 250 258 215 CLH 004 006 007 215 240 182 174 206 216 174 245 287 213 203 235 258 203 204 206 207 Not available Not available Not available 008 011 014 016 275 339 258 279 258 279 238 257 215 215 2...

Страница 25: ...11 014 016 174 197 201 219 232 242 261 325 332 287 287 145 165 175 137 125 135 143 145 158 169 145 165 175 137 206 248 251 219 232 242 261 325 332 287 287 145 165 175 137 148 170 179 145 158 169 145 1...

Страница 26: ...268 288 298 257 SLH 004 006 007 227 253 196 199 229 245 199 256 299 225 229 259 289 229 204 206 207 Not available Not available Not available 008 011 014 016 290 357 285 306 285 306 269 297 257 257 2...

Страница 27: ...nfiguration Support kit code Single support code Kit support pieces CBH 204 206 207 004 006 007 CLH 204 206 004 006 CQH 204 004 SBH 204 206 207 004 006 007 SLH 204 206 004 006 SQH 204 004 485620 4 CBH...

Страница 28: ...GAS MALE ON 204 206 207 MODELS TANK VERSION WITH WITHOUT PUMP IS NOT AVAILABLE 204 206 207 204 206 207 HEAT RECOVERY WATER CONNECTION OPTIONAL 016 016 LATERAL VIEW ONLY FOR CQH 016 SBH 007 AND SBH 01...

Страница 29: ...ion 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater Std with pressure transducer High pressure manometer Opt Low pressure manometer Opt Safe...

Страница 30: ...11 4 11 4 H 2 2 2 21 2 21 2 21 2 21 2 Refrigerant components Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heat...

Страница 31: ...Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor High pressure switch HP Low pressure switch LP Crankcase heater High pressure manometer Opt Low pressure manometer Opt Saf...

Страница 32: ...QH SBH SLH SQH 204 206 207 008 011 014 016 G 2 2 2 21 2 21 2 21 2 21 2 H 2 2 2 21 2 21 2 21 2 21 2 Refrigerant components Item Description Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Compressor...

Страница 33: ...ents Item Description Item Description 1 2 3 4 5 6 7 8 9 10 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve E...

Страница 34: ...7 8 9 10 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve Drain valve 11 12...

Страница 35: ...3 4 5 6 7 8 9 10 11 12 13 Evaporator Evaporator antifreeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve D...

Страница 36: ...freeze heater Opt Rubber flexible pipe only with pumps and or tank Manual air valve Gate valve Pump Safety valve Expansion tank Service ball valve Drain valve Control temperature sensor Antifreeze tem...

Страница 37: ...d Le Fabricant d clare que ce produit est conforme aux directives Europ ennes El Fabricante declara que este producto es conforme a las directivas Europeas O Fabricante declara que este produto est em...

Страница 38: ...of EMERSON Tel 39 049 9719111 Telefax 39 049 5841257 Internet www liebert hiross com Printed in Italy by Liebert HIROSS S p A Issued by T D Service Since the Liebert HIROSS Company has a policy of co...

Отзывы: