Part 4 Trouble Shooting
- 73 -
Copyright © 2019 - 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Cause of
Trouble
Condition
Mechanism of Fault Generation
Generation
of refrigerant
flow distur-
bance
Bending/Blocking of a pipe
EEV fault Closing of SVC Valve
Freezing of indoor device
→
Reduced evaporation temperature due to
excessive expansion of refrigerant.
Weak heating and cooling
→
Insufficient flow of refrigerant
Frequent turning on/off of the compressor by
the high/low pressure protection logic
→
Accumulated refrigerant elevates the tem-
perature and reduces the pressure.
Wrong oil collection elevates the outlet tem -
perature of the compressor and damages the
compressor.
■
Bending/Blocking of a pipe
■
Checking SVC Valve
Bending of a pipe
OPEN
Check pipes
SVC Valve
Check
EEV Check
Replacing a part of or
the entire pipes
SVC Valve Full Open
Replacing EEV
❈
EEV Checking Method :
Check the opening/closing
sound of EEV when the power
is applied for the first time.
Generation of refrigerant flow disturbance
6.7 Troubleshooting Outdoor Error
CH 21 (DC Peak / Comp IPM Fault)