Part 4 Trouble Shooting
- 54 -
Copyright © 2019 - 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
2. Pump Down
Setting Procedure
1) Set the DIP Switch as follow after shutting the power source down.
2) Reset the power.
3) Red LED and Green LED of PCB lights during work.
(The indoor unit is operated by force.)
4) If operation is done, Red LED will be turned off.
If operation is not done normally, Red LED will blink.
5) Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine).
Then close the gas valve after Green LED on.
UUB1, UUC1
UUD1, UUD3
1
2
3
4
5
6
5