- 52 -
Copyright © 2019 - 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
1.2 Error Indicator (Outdoor)
1 Time
1 Time
1 Time
2 Times
2 Times
2 Times
1 second
2 seconds
2 seconds
1 second
1 second
LED01G
(RED)
LED02G
(GREEN)
Standard Inverter : 18k
Compact Inverter : 24k/30k
2.5 seconds
1 second
1 second 2.5 seconds
LED 1
(RED)
1 second
Part 4 Trouble Shooting
1. Self-diagnosis Function
1.1 Error Indicator (Indoor)
Operation Indicator Lamp
Indoor Error
Lamp
Forced operation button
Description
Lamp Color
Cooling mode
Green
Heating mode
Green
Time to clean filter in cooling/heating Mode
Yellowish Green
Time to clean filter when product is not operating
Orange
Hot start or defrost mode before starting heating mode
Green
When reservation set on
Yellowish Green
Code
Title
Cause of Error
1
Air temperature sensor of Indoor unit
Air temperature sensor of indoor unit is open or short
2
Inlet pipe temperature Sensor of indoor unit
Inlet pipe temperature sensor of indoor unit is open or short
3
Communication error : wired remote
controller
↔
indoor unit
Failing to receive wired remote controller signal in indoor unit
PCB
4
Drain pump
Malfunction of drain pump
5
Communication error : outdoor unit
↔
indoor unit
Failing to receive outdoor unit signal in indoor unit PCB
6
Outlet pipe temperature sensor of indoor unit
Outlet pipe temperature sensor of indoor unit is open or short
9
Indoor EEPROM Error
In case when the serial number marked on EEPROM of Indoor
unit is 0 or FFFF
10
Abnormal fan motor operation
Disconnecting the fan motor connector / Failure of indoor fan
motor lock
Standard Inverter :
9k/12k/24k/36k/42k/48k/60k
Compact Inverter : 18k
Code
Title
Operating state
Error display
-
Air purification panel fault related
error
Product (operation) /
air purify function
(stop)
When air purify function is activated, the indoor
buzzer sounds 7 times (Buzzer sounds in 3 hour
units, air purify function turns off after 9 hours)