- 95 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
2. CT Sensing Check
• Inspecting PCB phase current sensing circuit
1. Set Multi-tester DC voltage measurement mode.
2. Mesure the below mesureing point DC voltages at Power-on standby state.
3. If the measurements are outside DC 2.5V ± 0.2V, the parts are decided as burned.
3. Connector Check
U
V
W
<WVC connector check>
<CT Sensing Check Point>
GND
Black
Red
Vdc