- 111 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
73
AC Input Instant over
Current Error
PCB(Inverter) input
current is over
100A(peak) for 2us
1. Overload operation (Pipe clogging/Covering/EEV
defect/Ref. overcharge)
2. Compressor damage (Insulation damage/Motor
damage)
3. Input voltage abnormal (L,N)
4. Power line assemble condition abnormal
5. PCB assembly 1 Damage
(input current sensing part)
Display
code
Title
Cause of error
Check point & Normal condition
h
PFCM Moudle checking method
①
Set the multi tester to diode mode.
②
Check short between input signal pin which are
placed below PFC Module
③
Replace PCB assembly 1 if it is short between pins
except No.4,5 pins.
CAUTION
PFCM module No.4,5 pins are internal short state.
No
1.Check Pipe clogging/distortion
2.Check Covering (Indoor/Outdoor Unit)
3.Check EEV connector assemble condition/normal operation
4.Check refrigerant pressure
→
Reassemble or manage if abnormality found
Is installation
condition normal?
Is compressor
Wire connection
condition normal?
1.Check PCB assembly 1 U,V,W connector connection condition
2.Check wire disconnection and wiring
3.Check compressor terminal connection condition(bad contact)
→
Reassemble if abnormality found
Is AC input Wire connection
condition normal?
1.Check L,N connection condition
2.Check wire disconnection and wiring
→
Reassemble if abnormality found
Is PCB assembly 1
normal?
Yes
No
Recheck power and
installation condition
Yes
Yes
Yes
No
No
Yes
No
Check
(ZHBW**6A0)
L-N phase voltage is 230±15%
(ZHBW**8A0)
R-S-T-N phase voltage is 380±15%
→
Check connection condition and wiring if power is abnormal
Is input voltage normal?
Check PCB assembly 1 PFCM normality
→
Replace PCB assembly 1
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
n
Error Diagnosis and Countermeasure Flow Chart