Common Setting
• Function Code 01
: Test Run
Test run should be performed when additional refrigerant charging is required. To charge the refrig-
erant, the product must run in Cooling mode. Test run instantly makes the product working in Cool-
ing mode for 18 minutes.
Note
: • If you press any kind of button during this mode, Test Run mode will be finished.
• After running 18 minutes under test run mode, system will automatically turn OFF.
• Function Code 02
: Disable 3 minute Delay
Factory use only.
• Function Code 03
: Remote Air Sensor Connection
If user connects remote air sensor to control the product by room air temperature, the connection
information should be notified to the product.
Note
: If remote air sensor is connected but this function code is not set correctly, the product can
not be controlled by room air temperature.
• Function Code 04
: Celsius/Fahrenheit Switching
Temperature is displayed in Celsius or Fahrenheit.
• Function Code 05
: Setting Temperature Selection
The product can be operated according to air temperature or leaving water temperature. The selec-
tion for setting temperature as air temperature or leaving water temperature is determined.
Note
: Air temperature as setting temperature is ONLY available when Remote Air Sensor Connec-
tion is enabled and Function Code 03 is set as 02.
• Function Code 06
: Auto Dry Contact
This function allows the Dry contact-indoor unit operate under Auto Run mode or Manual mode with
remote control panel.
If thermostat is used, value should be changed from "2" to "1"
• Function Code 07
: Address Setting
When Central Controller is installed, address assigning is set by this function.
System Set-Up
84