Piping and Wiring for Outdoor Unit
After checking and confirming following conditions, start wiring work.
1. Secure dedicated power source for the Air-to-Water heat pump. The wiring diagram (attached
inside the control box of the indoor unit) is presenting related information.
2. Provide a circuit breaker switch between power source and the outdoor unit.
3. Although it is very rare case, sometimes the screws used to fasten internal wires can be loosen
due to the vibration while product transportation. Check these screws and make it sure if they
are all fastened tightly. If not tightened, burn-out of the wire can be occurred.
4. Check the specification of power source such as phase, voltage, frequency, etc.
5. Confirm that electrical capacity is sufficient.
6. Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7. Confirm that the cable thickness is as specified in the power sources specification. (Particularly
note the relation between cable length and thickness.)
8. Provide an ELB(electric leakage breaker) when the installation place is wet or moist.
9. The following troubles would be caused by abnormal voltage supply such as sudden voltage in-
creasing or voltage drop-down.
• Chattering of a magnetic switch (frequent on and off operation)
• Physical damage of parts where magnetic switch is contacted
• Break of fuse
• Malfunction of overload protection parts or related control algorithms.
• Failure of compressor start up
10. Ground wire to ground outdoor unit to prevent electrical shock.
CAUTION
When connecting power cable, make sure the
rubber bushes are properly attached in knock-out
holes after removing the Insulation pad.
Control Terminal
(Terminal for
Connecting Cable)
Main Power
Terminal
(Terminal for
Power Cable)
Cable Clamp
(or Cord Clamp)
Cable Clamp
(or Cord Clamp)
Insulation pad
Side Panel
Water
Inlet
Water
Outlet
46
Air-to-Water Heat Pump
Wiring Procedure for Power Cable and Connecting Cable
Step 1.
: Disassemble the side panel from the outdoor unit by loosing screws.
Step 2.
: Connect Power cable to Main Power Terminal and Connecting cable to Control Termi-
nal, respectively.
See below figure for detailed information. When connecting earth cable, the diameter
of cable should be bigger than 1.6mm
2
to secure safety. The earth cable is connected
to the terminal block where earth symbol is marked.
Step 3.
: Use cable clamps (or cord clamps) to prevent unintended move of Power cable and
Connecting cable.
Step 4.
: Reassemble the side panel to the outdoor unit by fastening screws.
Содержание Therma V AHUW096A2
Страница 97: ......