22
COMMUNICATION KIT INSTALLATION
E
N
G
L
IS
H
R
Ro
otta
arry
y S
S/
/W
W
ڸ
ڸ
ڸ
ڹ
ڹ
ڹ
Rotary S/W
Dip S/W(SW03)
④
Room Temperature control from DDC or Rotary S/W
h
According to Dip S/W(SW03) Setting, you can set up the Function of Room Temperature control.
Dip S/W(
②
SW03)
Function
Setting
Dip S/W
No 1
ON
RS485 Communication with Single CAC
OFF
Not available
No 3
ON
Possible to control Room Temperature Function (Default)
OFF
Only Monitoring (DO Signal only is enable)
No 4
ON
DDC Control (Wiring No. AI 10-4)
OFF
Rotary S/W(SW_TYPE) Control
No 6
ON
Room Temperature Default setting (Cooling 18°C, Heating 30°C)
OFF
Room Air(or return air) temperature control using Al signal and Rotary S/W
• Dip S/W(SW03) NO 4 : OFF
Rotary
S/W(
①
) Number
Room Temp.(°C) Cooling
Room Temp.(°C) Heating
0
Not available
Not available
1
18
16
2
18
17
3
18
18
4
19
19
5
20
20
6
21
21
7
22
22
8
23
23
9
24
24
A
25
25
B
26
26
C
27
27
D
28
28
E
29
29
F
30
30