BEFORE INSTALLATION
11
E
N
G
L
IS
H
CAUTION
Selection of Evaporator(AHU)
See table below for applicable units
Selecting the capacity setting 'Option PCB'(Accessory) according to the capacity mentioned
below.
- The corresponding capacity setting 'Option PCB' needs to be selected depending on the
need capacity.
- After checking the need capacity, remove the 24 k Option PCB equipped in the main PCB,
and set up the Option PCB fitted the need capacity in the main PCB.
* Evaporator Saturated Temperature(SST) = 6 °C, SH (Superheat) 5K, Air Temperature =
27 °C DBT / 19 °C WBT
* Heat exchanger volume [m
3
] : Pipe cross-section × Tube length
-. Pipe cross-section [m
2
] =
π
× ID
2
/4
-. Tube length [m] = Tube length of 1 pipe × Tube step × Tube row
!
Capacity setting
'Option PCB'
Detail
Option PCB
P/NO
Capacity
(Btu/h)
Standard heat
exchanger volume
(10
-3
× m
3
)
Maximum heat
exchanger capacity
(kW)
Air Flow rate
(CMM)
EBR65102902
18 k
2.4
5.0
13~16.5
EBR65102903
24 k
2.6
7.1
14~18
EBR65102904
30 k
2.9
8.0
20~26.5
EBR52358920
70 k
5.2
20.0
60~70
EBR52358921
85 k
5.9
23.0
64~80