TI V S System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Model Numbers
3.0 Ton
4.0 Ton
4.4 Ton
ARUN038GSS4
ARUN048GSS4
ARUN053GSS4
Cooling Performance
1RPLQDO&RROLQJ&DSDFLW\%WXK
1
39,500
50,000
55,500
5DWHG&RROLQJ&DSDFLW\%WXK
2
38,000
48,000
53,000
Heating Performance
HDWLQJ&DSDFLW\%WXK
1
44,000
56,500
61,500
5DWHG+HDWLQJ&DSDFLW\%WXK
2
42,000
54,000
59,000
Operating Range
&RROLQJ)'%
23 - 122
23 - 122
23 - 122
+HDWLQJ):%
-4 - 61
-4 - 61
-4 - 61
Compressor
Inverter Quantity
DC Inverter Starting
DC Inverter Starting
DC Inverter Starting
2LO7\SH
PVE / FVC68D
PVE / FVC68D
PVE / FVC68D
Fan (Side Discharge)
Type
Axial Flow Fan
Axial Flow Fan
Axial Flow Fan
0RWRU2XWSXWN:[4W\
0.124 x 2
0.124 x 2
0.124 x 2
0RWRU'ULYH
Brushless Digitally Controlled / Direct
2SHUDWLQJ5DQJH530
Cooling
0 - 850
0 - 850
0 - 850
Heating
0 - 850
0 - 850
0 - 850
0D[LPXP$LU9ROXPH&)0
3,885
3,885
3,885
Unit Data
Refrigerant Type
R410A
R410A
R410A
5HIULJHUDQW&RQWURO/RFDWLRQ
EEV / Indoor Unit
EEV / Indoor Unit
EEV / Indoor Unit
0D[1XPEHU,QGRRU8QLWV6\VWHP
3
6
8
9
6RXQG3UHVVXUHG%$
4
50
51
52
1HW8QLW:HLJKWOEV
207
207
207
6KLSSLQJ:HLJKWOEV
218
218
218
Communication Cables
5,6
2 x 18
2 x 18
2 x 18
Heat Exchanger
0DWHULDODQG)LQ&RDWLQJ
Copper Tube / Aluminum Fin and GoldFin™ / Hydrophilic
5RZV)LQVSHULQFK
2 / 14
2 / 14
2 / 14
Piping
7
/LTXLG/LQH&RQQHFWLRQLQ2'
3/8 Braze
3/8 Braze
3/8 Braze
9DSRU/LQH&RQQHFWLRQLQ2'
5/8 Braze
5/8 Braze
3/4 Braze
)DFWRU\&KDUJHOEVRI5$
6.6
6.6
6.6
Table 1:
9+HDW3XPS8QLW6SHFL¿FDWLRQV
1
Nominal capacity applied with non-ducted indoor units, and is rated 0 ft. above sea level
with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and
indoor units. All capacities are net with a Combination Ratio between 95–105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 59ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
2
5DWHGFDSDFLW\LVFHUWL¿H5,6WDQGDUG6HHZZZDKULQHWRUJIRULQIRUPDWLRQ
3
The System Combination Ratio must be between 50–130%.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded or
unshielded (if shielded, must be grounded to chassis at ODU only), and must comply with
applicable local and national codes.
6
3RZHUZLULQJFDEOHLV¿HOGSURYLGHGDQGPXVWFRPSO\ZLWKWKHDSSOLFDEOHORFDODQGQDWLRQ
-
al codes. See below for detailed electrical data.
7
Refer to the Refrigerant Piping section of this manual for correct line sizing. Contractor
must use LG manufactured Y-Branch and Header Kits only. Designer must verify refriger-
DQWSLSLQJGHVLJQFRQ¿JXUDWLRQXVLQJ/*¶VFRPSXWHUL]HGUHIULJHUDQWSLSLQJ/$760XOWL9
software to validate the pipe design.
Table 2: 208-230V Heat Pump Unit Electrical Data.
Nominal Tons
Unit Model No.
Compressor Motor
&RQGHQVHU)DQ0RWRU
MCA
MOCP
Quantity
Motor Amps
)DQ4W\
Amps
5/$(D
)/$(D
3.0
ARUN038GSS4
1
19.5 2
1.0
25
40
4.0
ARUN048GSS4
1
23.1 2
1.0
30
50
4.4
ARUN053GSS4
1
25.2 2
1.0
33
50
0XOWL962XWGRRU8QLW6SHFL¿FDWLRQV(OHFWULFDO'DWD
GENERAL DATA