Refrigerant Piping Connections
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
0LQLPXPQXPEHURIFRQQHFWHGDQGRSHUDWLQJLQGRRUXQLWVLV
0D[LPXPQXPEHURILQGRRUXQLWVRQDV\VWHPLV
• ARUN038 = 6
• ARUN048 = 8
• ARUN053 = 9
IDU = Indoor Unit
ODU = Outdoor Unit
All elevation limitations are measured in actual feet
ELF = Equivalent length of pipe in feet
Copper Tubing Size
2'
Equivalent Pipe Length*
Standard 90° Elbow
0.6
0.9
1.3
1.6
1.9
2.5
Long Radius 90° Elbow
0.4
0.6
0.8
1.0
1.3
1.7
Street 90° Elbow
1.0
1.6
2.1
2.6
3.1
4.2
Standard 45° Elbow
0.3
0.5
0.7
0.8
1.0
1.3
Street 45° Elbow
0.5
0.8
1.1
1.4
1.6
2.2
Y-Branch
1.6
1.6
1.6
1.6
1.6
1.6
Header
3.3
3.3
3.3
3.3
3.3
3.3
%DOO9DOYH
The equivalent length of a FULL port ball valve is the physical length of the valve. In other words, treat as straight
pipe. A full port ball has the same bore diameter as the connected pipe.
Table 16:
)LHOG6XSSOLHG5HIULJHUDQW)LWWLQJV²/LTXLG/LQH(TXLYDOHQW3LSH/HQJWK
(TXLYDOHQWSLSHOHQJWK±7KHVXPRIWKHDFWXDOSLSHOHQJWKSOXVDOORFDWLRQVIRUSUHVVXUHGURSWKURXJKHOERZVYDOYHVDQGRWKHU¿WWLQJVLQHTXLYDOHQWOHQJWK
Values calculated based on formula and factors from www.sporlanonline.com.
/*VXSSOLHG<%UHDGHU¿WWLQJVPXVWEHXVHG)LHOGEXLOW<%UHDGHU¿WWLQJVDUHQRWSHUPLWWHG
Pipe Length
Longest total
984 ELF
Longest distance
from ODU to IDU
492 feet (Actual)
574 feet (Equivalent)
Distance Between
Fittings and IDUs
´(/)
0LQLPXPGLVWDQFHEHWZHHQ
IDU to any Y-Branch
(/)
0D[LPXPGLVWDQFHEHWZHHQ
first Y-Branch to farthest IDU
131 feet
0LQLPXPGLVWDQFHIURP
IDU to Y-Branch
3 feet
Elevation
If ODU is above IDU
164 feet
If ODU is below IDU
131 feet
Between any two IDUs
49 feet
Table 17:
0XOWL96/LTXLG3LSLQJ'HVLJQ3DUDPHWHUV
Total Piping Length Cannot Exceed 984 Feet
Longest Piping Length After First Branch
Maximum 131 Feet
Level Difference Between IDU and IDU
Maximum 49 Feet
Outdoor Unit
Longest Piping Length
Maximum 492 Feet (Actual)
Maximum 574 Feet (Equivalent)
If the Outdoor Unit Is Mounted Below the Indoor Unit(s)
Figure 32:
0XOWL963LSLQJ6\VWHP&RQ¿JXUDWLRQ/LPLWDWLRQV
If the Outdoor Unit is Mounted Above the Indoor Unit(s)
Longest Piping Length
Maximum 492 Feet (Actual)
Maximum 574 Feet (Equivalent)
Actual Pipe Length—Actual Physical Length of a Pipe
Level Difference Between IDU and IDU
Maximum 49 Feet
Level Difference Between
ODU and IDU
Maximum 164 Feet
Total Piping Length Cannot Exceed 984 Feet
Outdoor Unit
Longest Piping Length After First Branch
Maximum 131 Feet
REFRIGERANT PIPING CONNECTIONS
5HIULJHUDQW3LSLQJ6\VWHP([DPSOHV