Liquid Piping
Vapor Piping
Manifold Gauge
Low Pressure
Side Handle
High Pressure
Side Handle
Refrigerant Charge
• Both vapor and liquid piping to be vacuumed.
• Always add the appropriate amount of refrigerant when adding an
additional refrigerant charge. Too much or too little refrigerant will
cause system malfunction.
If the added refrigerant charge is more than 10% over the neces-
sary amount, indoor unit operation may malfunction.
If the added refrigerant charge is more than 10% over the necessary
amount, the condenser will rupture, which may cause physical injury
or death.
DANGER
Table 27:
7RWDO0XOWL962XWGRRU8QLW5HIULJHUDQW&KDUJH
Nominal Tons
Model Number
5HIULJHUDQW&KDUJHOEV
3.0
ARUN038GSS4
6.6
4.0
ARUN048GSS4
6.6
4.4
ARUN053GSS4
6.6
6HHWKH&DXWLRQVIRU5HIULJHUDQW/HDNVVHFWLRQRQSDJHV
- 72.
REFRIGERANT PIPING CONNECTIONS
Refrigerant Charge
Calculating the additional refrigerant charge must also take into account piping length.
$GGLWLRQDO5HIULJHUDQW&KDUJH)RUPXOD
0XOWL962XWGRRU8QLW)DFWRU\5HIULJHUDQW&KDUJHOEV$GGLWLRQDO&KDUJHOEV7RWDO$GGLWLRQDO5HIULJHUDQW$PRXQWOEV
Where Additional Charge (lbs.) =
+ Total liquid piping length (feet) @ 7/8 inches x 0.238 lbs./ft.
+ Total liquid piping length (feet) @ 3/4 inches x 0.179 lbs./ft.
+ Total liquid piping length (feet) @ 5/8 inches x 0.116 lbs./ft.
+ Total liquid piping length (feet) @ 1/2 inches x 0.079 lbs./ft.
+ Total liquid piping length (feet) @ 3/8 inches x 0.041 lbs./ft.
+ Total liquid piping length (feet) @ 1/4 inches x 0.015 lbs./ft.
+ Correction Factor (CF) (lbs.)
([DPSOH
Additional Charge =
A (131 ft.) x 0.041 lbs./ft. (for 3/8 in. piping)
+ B (66 ft.) x 0.041 lbs./ft. (for 3/8 in. piping)
+ C (66 ft.) x 0.041 lbs./ft. (for 3/8 in. piping)
+ a+b+c+d+e (33 ft.+33 ft.+33 ft.+33 ft.+33 ft.) x 0.015 lbs./ft. (for 1/4 in. piping)
+ CF
= 5.37 (A) + 2.71 (B) + 2.71 (C) + 2.46 ([a+b+c+d+e] x 0.015) + 0 (CF) = 13.3
If the calculation results in a negative number, refrigerant
does not need to be added.
Figure 42: Example of Additional Refrigerant Charge Calculation.
A = 131 ft. @ 3/8 in.
B = 66 ft. @ 3/8 in.
C = 66 ft. @ 3/8 in.
X
b = 33 ft. @ 1/4 in.
a = 33 ft. @ 1/4 in.
c = 33 ft. @ 1/4 in.
d = 33 ft. @ 1/4 in.
e = 33 ft. @ 1/4 in.
Multi V S Outdoor Unit
IDU
IDU
IDU
IDU
IDU
Figure 43: Charging the Refrigerant.