DIP Switch
LED
SW01C (
&RQ¿UP
)
SW02C (
%DFNZDUG
)RUZDUG
SW04C ( X : Cancel)
SW01D (Reset)
SW03C (
ON
OFF
Vacuum Mode
Vacuum mode is used for creating vacuum in the system after the compressor or other outdoor unit parts have been replaced, or if an indoor
unit has been added to or replaced.
Turn No. 5 on Outdoor Unit DIP Switch to ON.
6HOHFWWKHPRGHXVLQJWKHŹDQGŻEXWWRQV
Choose “SVC” by pushing the
Ɣ
button.
6HOHFWWKHIXQFWLRQXVLQJWKHŹDQGŻEXWWRQV
Choose “Se3” by pushing the
Ɣ
button.
Start the vacuum mode “VACC”. Outdoor Unit
valves and EEV should be open. Indoor Units
EEVs should be open.
9DFXXP0RGH2Q
Figure 39:
0XOWL962XWGRRU8QLW',36ZLWFK9DFXXP0RGH6HWWLQJDQG
PCB Location.
9DFXXP0RGH2II
Set DIP Switch No. 5 to Off, and push the reset
button on the Outdoor Unit PCB.
• All valves in the indoor and outdoor units will be opened when the
Vacuum Mode is set.
• Outdoor unit operation mode stops during Vacuum Mode; compres-
sor can’t operate.
• After moving and installing the system to another site, recharge the
refrigerant after perfect vacuum. If a different refrigerant or air is
PL[HG ZLWK WKH RULJLQDO UHIULJHUDQW WKH UHIULJHUDQW F\FOH PD\ PDO
-
function and damage the unit.
• Always add the appropriate amount of refrigerant when adding an
additional refrigerant charge. Too much or too little refrigerant will
cause system malfunction.
REFRIGERANT PIPING CONNECTIONS
Vacuum Mode