CUT SHEET
|
83
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
1
2
3
4
2
1
4
3
2
1
3
4
A
B
C
D
E
F
G
H
I
A
B
C
D
E
F
G
H
I
A
B
C
D
E
F
G
H
I
J
K
L
M
Figure 66: 036, 047, 053
Front Connections
Figure 69: 036, 047, 053
Front Connection Detail
Figure 67: 036, 047, 053
Rear Connections
Figure 70: 036, 047, 053
Rear Connection Detail
Figure 68: 036, 047, 053
Side Connections
Figure 71: 036, 047, 053
Side Connection Detail
ID
Description
Use
Notes
1
1.0” Knockout
• Power or communications conduit
• Liquid line connection
Use rubber or polymeric resin grommets.
2
1-1/4” Knockout
3
4”x5” Cutout
• Bundled pipe connection
• Power and communications wiring
• Keep pests out.
Fill area around pipe bundle with spray foam and suitable weather tight cover.
• Gasket rough metal edges to protect pipe and wire chaf
fi
ng.
4
4”x2” Cutout
CUT-SHEET
Figure 64: 036, 047, 053 Piping
Options—Front/Side Connections
Figure 65: 036, 047, 053 Piping
Options—Rear Connections
Model
Liquid
Vapor
Conn
Type
Conn
Type
ARUN036GS2
3/8”
Braze
5/8”
Braze
ARUN047GS2
3/8”
Braze
5/8”
Braze
ARUN053GS2
3/8”
Braze
3/4”
Braze
Pipe and Electrical Connections
A
B
C
D
E
F
G
H
I
J
K
L
M
Front
1.0
2-1/4
4-1/8
5-3/16
6-3/8
1.0
1-7/8
4-1/8
4-11/16
—
—
—
—
Rear
1.0
2.0
3-7/8
5-3/16
6-3/8
1.0
1-7/8
3-11/16
4-11/16
—
—
—
—
Side
1.0
2-1/4
4-1/8
5-3/16
6-3/8
1.0
1-7/8
4-1/8
4-11/16
6.0
11-7/16
3-7/8
5-7/8
Table 35: Outdoor Unit Pipe Connections (in.)
Table 36:Outdoor Unit Wiring Connections
Table 37: ARUN 036, 047, and 053 Piping and Electrical Connection Dimensions (in.)