SYSTEM ENGINEERING
|
77
HEA
T PUMP
CONDENSING UNIT ENGINEERING MANUAL
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
JOBSITE CONNECTIONS
ARUN 036, 047, 053
Note:
1. For detailed information, refer to "Dimensional Data and Weights" on page 3 and "Pipe and Electrical Connections" on page 4
for exact location of pipe and electrical connections.
2. Minimum 18 AWG, shielded, stranded, 2 conductor or size per local code (whichever is larger).
3. Refer to Table 2 on page 15 for full load ampere ratings. Size all wiring and
fi
eld-provided components per local codes.
Power Wiring
Route control wiring and power wir-
ing in separate conduits.
All wiring must conform to NEC and
local codes.
Unit disconnect and wiring is field
supplied.
Communication
Cables
See Figure 55, Figure 56, and
Figure 57.
See page 74 for all low voltage
wiring termination details.
Lightning Protection
Field-supplied where applicable.
Installed per local code.
Fused Disconnect
provided by others
Figure 54: System
Control Board
Figure 55:
Communication
Ground Termination
2
Figure 56: Power Wire Terminations
L1 = left
L2 = center
Earth Gnd = right
Figure 57: Communication
Cable Separated from Power
Wiring
Figure 58: Refrigerant Pipe
Connection Point
1
Figure 59: Refrigerant
Pipe and Electrical
Knockouts