System Engineering
80
|
SYSTEM ENGINEERING
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Refrigerant Charge—ARUN 036, 047, 053
MINI REFRIGERANT CHARGE
Table 33: System Refrigerant Charge Calculator (lbs.)
Job Name_______________________________________
System Tag or ID____________________________________ Project Manager__________________________________
Date___________________________________________
Line #
Description/Style
Chassis ID
Size
Quantity
R410A Charge/Unit
Total (lbs.)
1
Linear feet of 1/4” liquid line tubing
1
0.015
2
Linear feet of 3/8” liquid line tubing
1
0.041
3
Linear feet of 1/2” liquid line tubing
1
0.079
4
Wall M ArtCool Mirror
SE
7k to 15k
0.53
5
Wall M ArtCool Mirror
S8, S5
18k to 24k
0.62
6
1-Way Cassette
TJ
7k to 12k
0.44
7
2-Way Cassette
TL
18k to 24k
0.35
8
4-Way Small Cassette
TR
5k to 7k
0.40
9
4-Way Small Cassette
TR
9k to 12k
0.55
10
4-Way Small Cassette
TQ
15k to 18k
0.71
11
4-Way Large Cassette
TN
9k to 15k
1.06
12
4-Way Large Cassette
TM
18k to 24k
1.41
13
4-Way Large Cassette
TP
24k to 28k
1.06
14
4-Way Large Cassette
TN
36k
1.41
15
4-Way Large Cassette
TM
42k to 48k
1.41
16
High Static Ducted
BH
7k to 24k
0.57
17
High Static Ducted
BG
15k to 42k
0.97
18
High Static Ducted
BR
48k
1.37
19
Low Static Ducted
B1, B3
7k to 15k
0.37
20
Low Static Ducted
B2, B4
18k to 24k
0.82
21
Vertical Air Handler
NJ
18k to 24k
1.04
22
Vertical Air Handler
NJ
30k
1.04
23
Vertical Air Handler
NJ
36k
1.57
24
Vertical Air Handler
NK
42k to 54k
2.00
25
Ceiling Suspended
VJ
18k to 24k
0.77
26
Convertible Surface Mount—Ceiling/Wall
VE
9k to 12k
0.22
27
Floor Standing
CE
7k to 15k
0.37
28
Floor Standing
CF
18k to 24k
0.82
29
ARUN 036 ODU
-1.1
30
ARUN 047 ODU
0
31
ARUN 053 ODU
0
Trim Charge (lbs) (sum lines 1–30)
ODU Factory Charge ARUN 036, 047, 053
6.6
System Charge, Total of Trim and Factory Charge (lbs)
1. For charging purposes, consider only the liquid line, ignore the vapor line.
3. If trim charge is negative, remove refrigerant.
2. Maximum quantity of indoor units allowed:
ARUN 036 = 6
ARUN 047 = 8
ARUN 053 = 9
4. If trim charge is positive, add refrigerant.
5. Take appropriate actions at the end of the equipment's
useful life to recover, recycle, reclaim, or destroy R410A
refrigerant according to applicable US EPA rules.