System Engineering
78
|
SYSTEM ENGINEERING
Due to our policy of continuous product innovation, some specifications may change without notification.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
A.
Use 2-conductor stranded and shielded wire
with the shield grounded at the outdoor unit.
B.
Connect the communications cable between
indoor units using a daisy chain con
fi
gura-
tion only. “Star” or “home run” control wiring
connections involving soldering or wire caps
are not permitted.
C.
Minimum 18 AWG, 2 conductor stranded
shielded copper cable only.
D.
Provide separate conduits for control wiring
and power wiring.
E.
Power and communications cables must
not be routed in the same conduit and must
be routed in a manner that does not cause
communication problems. For more
information, refer to Table 29 on page 75.
F.
Connect outdoor unit terminal IDU-A to
the odd numbered indoor unit terminal.
Terminal “A” on the indoor units may be
tagged 3(A) or 5(A).
G.
Connect outdoor unit terminal IDU-B to in-
door unit terminal “B”. Terminal “B” on the
indoor units may be tagged 3(B) or 5(B).
H.
Maximum allowed length of indoor unit com-
munication cable is 984 feet.
1
2
3
4
5
6
7
8
9
10
GND
DRY 2
DRY 1
Internet A
Internet B
IDU-A
IDU-B
SODU-A
SODU-B
Fan Only/Cool/Heat
Selector Switch or customer
supplied system shutdown
switch—See the "Controls"
section starting on page 83 for
more information
Central Control and Build-
ing Automation System
Communication Buss
Connection—Connect LG
Central Controller and/or
BMS gateway products
Indoor Unit(s)—
Communication Buss Con-
nection—See Figure 61
Not used with Multi V Mini
12V
JOBSITE CONNECTIONS
IDU-A
IDU-B
5A 6B
5A 6B
5A 6B
3A 4B
3A 4B
3A 4B
Figure 73 – MultiV System – Daisy-Chain Communications Cable Wiring
Figure 61: Multi V System—Daisy-Chain Communications Cable Wiring
Power source for selected
controllers
Note:
1. Communications cable shield is grounded at ODU only.
2. Maintain polarity throughout the communication network.
Low Voltage Wiring
Figure 60: Communications Wiring Terminals
Ground