4
Vacuum pump
Valve must be closed
after achieving a vacuum
Charging
the cylinder
Refrigerator
System
Refrigerant
Loading tube
Valve should be open
when refilling the gas
Figure # 5
To know the refrigerant amount that contains and that it’s
necessary to be charged to the system, review the
graduated scale cylinder. For example, if we have 750
grams Freon in the cylinder and we must charge 165
grams to the system, this amount will be reached when the
cylinder indicator shows 585 grams. Remember that the
charge indicator shows a lower lever than real. Do this
after select the scale that corresponds to gas pressure
indicated in the pressure meter attached in the column
upper part.
Before performing this operation, make sure that the valve
attached between the vacuum pump and recharge
cylinder is closed in order to keep the Freon to be charged
into the system (see Figure #5).
To make R-134a flow to the system, open the valve which
is attached in the cylinder base and is connected to the
filling tube. The Freon gas amount must not be completely
charged in one session because it could block the
compressor motor; therefore, charge 20~30 grams and
immediately close the valve, the pressure increase and
the compressor motor start the suction, this make
pressure decrease, open the valve again and repeat the
previous steps until rise the established amount of R-134a
gas for the system. When the system is under operation,
the suction pressure must stabilize between 0.30 and 0.6
atmosphere of pressure.