– 18 –
5. OPERATION DETAILS
(1) The function of main control
1. Time Delay Safety Control
• 3min...
The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 3sec...
The indoor fan is ceased for 1~3 seconds to prevent relay noise.
(Protection of fan relay and micro chip)
• 1min...
The 4-way valve is ceased for 30 sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode.
2. Airflow Direction Control
• This function is to swing the louver left and right automatically and to set it at the desired position.
• The procedure is as the following.
1st : Press the ON/OFF Button to operate the product.
2nd : Press the Airflow Direction Control Button to swing the louver left and right automatically.
(Remote controller)
3rd : Repress the Airflow Direction Control Button to set the louver as the desired position.
(Remote controller)
3. Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the
controller and the operation diagram is as following
Intake Air temp.
Setting Temp. +1
°
C
(Compressor ON)
Setting Temp. -1
°
C
(Compressor OFF)
Indoor Fan Speed
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
3 minutes
3 minutes
Compressor
ON
OFF
ON
OFF
ON
Содержание LP-E5020CL
Страница 12: ... 12 3 LP E5020CL LP E5022CL CA WIRING DIAGRAM ...
Страница 13: ... 13 4 LP E5022HL HA ...
Страница 66: ... 66 10 ELECTRONIC CONTROL DEVICE 10 1 MAIN P C B ASM ...
Страница 68: ... 68 11 1 Circuit and Troubleshooting 11 SCHEMATIC DIAGRAM ...
Страница 71: ... 71 6 51 49 47 44 50 14 11 11 1 12 10 10 1 8 9 9 1 9 2 46 42 40 48 5 6 7 49 45 55 43 1 ...
Страница 79: ...P NO 3828A30074N Printed in Korea ...