5. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as
following.
Intake Air Temp.
Setting Temp.
(Compressor ON)
Setting Temp. -1
°
C
Indoor Fan Speed
Compressor
Electric Heater(Option)
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
Hot
Start
minimum
10sec.
minimum
1min
minimum
10sec.
OFF
A
A
OFF
LOW
LOW
LOW
Setting Temp. +1
°
C
(Compressor OFF)
Selecting
fan speed
Selecting
fan speed
• A point: The indoor pipe temperature to be less then 35°C or Discharge air Temperature to be less than 29°C.
The indoor fan operates for minimum 10sec. even if the indoor pipe temperature falls lower than35°C
or the discharge air Temperature falls lower than 29°C.
Low(
V
)
Stop(
VI
)
39˚C
Discharge Air Temp.
Indoor Pipe Temp.
34˚C
28˚C
26˚C
Selecting Fan Speed(
IV
)
Low(
II
)
Stop(
I
)
(Hot-Start Operating)
Heating Start
(Hot-Start Release Point)
Selecting Fan Speed(
III
)
¡
During heating operation, the operating procedure of the indoor fan is as the following.
Step
Indoor fan speed
Pipe temp.
Air discharge temp.
¥
Off
≤
28°C(Hot start operating)
–
¥–
Low
≥
28°C
<39°C
¥†
Selecting speed
≥
28°C
≥
39°C
¥‡
Selecting speed
≥
28°C
>34°C
¥·
Low
≥
26°C
≤
34°C
¥
Off
≤
26°C
–
Содержание LP-E5020CL
Страница 12: ... 12 3 LP E5020CL LP E5022CL CA WIRING DIAGRAM ...
Страница 13: ... 13 4 LP E5022HL HA ...
Страница 66: ... 66 10 ELECTRONIC CONTROL DEVICE 10 1 MAIN P C B ASM ...
Страница 68: ... 68 11 1 Circuit and Troubleshooting 11 SCHEMATIC DIAGRAM ...
Страница 71: ... 71 6 51 49 47 44 50 14 11 11 1 12 10 10 1 8 9 9 1 9 2 46 42 40 48 5 6 7 49 45 55 43 1 ...
Страница 79: ...P NO 3828A30074N Printed in Korea ...