52
4. CONTROL SYSTEM
ENGLISH
- Movement path :
Displayed item
Display status
Contact point status
Remark
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
for ice making
Optional
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Move to Main/Evaporator/Con-
denser/Compressor screen
Screen display button for
Compressor 2 status
Figure 34 Input status check screen
Table 7 Digital input display items
Chilled water flow interlock
Chilled water pump interlock
Remote operation signal
External fault signal
Condenser high pressure
Oil status
Motor status
Power supply status
Remote operation 2
Compressor startup check
Cooling water flow interlock
Cooling water pump interlock
Selecting ice making mode
Condenser high pressure 2
Oil status 2
Motor status 2
Power supply status 2
Compressor startup check 2
When in the ice making mode: Circuit closed
When run signal input is made: Circuit closed
When remote operation is made: Circuit closed
When there is an external problem: Circuit closed
When pressure is normal: Circuit closed
When flow rate is normal: Circuit closed
When compressor is normal: Circuit closed
When power supply is normal: Circuit closed
When remote operation is made: Circuit closed
When compressor is running: Circuit closed
When flow rate is normal: Circuit closed
When pump is running: Circuit closed
When in the Ice Making mode : Circuit closed
When pressure is normal: Circuit closed
When flow rate is normal: Circuit closed
When compressor is normal: Circuit closed
When power supply is normal: Circuit closed
When compressor is running: Circuit closed