4. CONTROL SYSTEM
51
ENGLISH
System information
- Movement path :
The screen displays the version of the program applied to the MICOM(Master, Slave and Display). "Program version
No." is shown for follow-up service and is useful for trouble shooting in case there is a problem in MICOM.
(1) Year, Month, Day, Day of the week, Hour, Minute and Second
Here, you can set the date and hour. The data will be the reference for information storage time, problem/caution
occurrence time and Scheduled r operation time.
Since it is the reference time for the MICOM operation, please make sure to check whether there is any deviation
from the present time.
(2) Operation data saving cycle
Here, you can set the operation data saving cycle. Operation data are the measured values by the sensors shown
in the basic screen, and saved on every time which was set in the operation data saving cycle when operation the
chiller. However, the problem data is saved in MICOM's memory regardless of the saving cycle.
(3) Screen brightness adjustment
This menu is for adjusting the brightness of LCD. Pressing 'Increase' key makes the figure increase making the
LCD brighter while pressing 'Decrease' key makes the figure decrease making the LCD darker.
Pressing 'End' key terminates adjustment of LCD brightness.
(4) Communication speed setting
The communication speed can be set in one of 9600bps, 19200bps or 38400 bps.
(5) Input status check
This menu displays ON(=circuit closed)/OFF(=circuit open) status of the digital input port. The menu is for check-
ing the status of the input signal contact point connected to the control panel of the chiller. When checking the
digital input status, it is required to refer to the control circuit diagram to prevent other signals entering the input
terminal of the micom.
If other communication lines are mixed in the connection, the board of the micom can be damaged.
Figure 33 System information
Содержание LCWW
Страница 119: ......