4. CONTROL SYSTEM
45
ENGLISH
(*) Display or application is allowed only when the chiller is designed for ice making(low temperature)
Item
Setting boundary
Standard set
value
Setting unit
Setting possible
time
Local/Scheduled
/Remote
Local
Always
Air conditioning
/Ice making
Air
conditioning
Always (*)
3.0 °C~ 30.0 °C
7.0 °C
0.1
Always
-20 °C~30 °C
5 °C
0.1
Always
1 °C~10 °C
2.0 °C
0.1
Always
0 ~ 3,600 seconds
200 second
1
Always
0 sec~ 360sec
2 seconds
1
Always
0.0 °C~10.0 °C
2.0 °C
0.1
Always
0.0 °C~10.0 °C
2.0 °C
0.1
Always
Used
/ Not used
Not used
Always
0.0 °C~10.0 °C
3.0 °C
0.1
Always
1~100%
100%
1
Always (**)
10.0~50.0 °C
32.0 °C
0.1
Always
1.0 °C~10.0 °C
4.0 °C
0.1
Always
0 ~ 3,600 seconds
0sec
1
Always
0 sec~ 360sec
0sec
1
Always
(4) Setting display screen
Operation mode setting
Control mode setting
Chilled water outlet temperature
Ice maker outlet temperature
Chilled water temperature P
Chilled water temperature I
Chilled water temperature D
Automatic operation temperature (set value+)
Automatic stop temperature (set value-)
Antifreeze operation function
Antifreeze operation temperature
Motor current limit
Cooling water inlet temperature
Cooling water temperature P
Cooling water temperature I
Cooling water temperature D
Table 6 Items in the user setting screen
Содержание LCWW