(3) Gas Charging
(After Evacuation)
• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect-
ed from the vacuum pump to the valve at the
bottom of the cylinder.
- If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
2. Purge the air from the charge hose.
- Open the valve at the bottom of the cylinder and
press the check valve on the charge set to
purge the air. (Be careful of the liquid refriger-
ant). The procedure is the same if using a gas
cylinder.
3. Open the low handle on the gauge and charge
the system with liquid refrigerant.
- If the system can not be charged with the speci-
fied amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from
the gas side valve's service port.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
5. Mount the valve stem nuts and the service port
nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
6. Apply steps from 1 to 5 to each unit (A, B, C, D,
E, F-unit) by the same method.
- 79 -
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
3-Way
valve
Open
3-Way
valve
manifold gauge
Charging
cylinder
Hi- handle
(CLOSE)
Low-handle
(OPEN)
Check valve
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
Содержание FMN0760NL
Страница 93: ... 93 Electronic Control Device 1 Indoor Unit 1 MAIN P C B ASM FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 94: ... 94 FMN1260NT FMN1860NT ...
Страница 95: ... 95 FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 96: ... 96 FMN1860NV ...
Страница 97: ... 97 2 Outdoor Unit MAIN P C B ASM FMU4480N6L ...
Страница 98: ... 98 PCB PWB ASSY SUB ...
Страница 99: ... 99 3 Display ASSY FMN1860NV FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 100: ... 100 4 SUB P W B ASSEMBLY FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 101: ... 101 Schematic Diagram 1 Indoor Unit FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 103: ... 103 FMN1260NFM B D ...
Страница 104: ... 104 FMN1860NV RY 4WAY RY OUTFAN ...
Страница 113: ... 113 354212 249951 268711 2 266010 352114 263230 352118 330870 158591 2 Cassette Type Indoor Unit FMN1260NT FMN1860NT ...
Страница 114: ... 114 346810 130411 359011 152311 135313 W0CZZ 137211 267110 352150 352150 130911 140570 268711 1 146811 ...
Страница 122: ...P No 3828A20208A August 2002 Printed in Korea ...