When indoor Fan does not operate.
Trouble 4
Check the SSR high speed operation by remote control.
(the Indoor Fan Motor is connected)
Turn off main power.
Check the connection of CN-FAN.
Check the Fan Motor.
Check the Fuse(AC250V, T2A).
Turn on the main power
Check the related circuit of indoor Fan Motor.
• The pin No. 38 of micom and the part for driving SSR.
• Check the related pattern.
• Check the SSR.
- SSR Open: Indoor Fan Motor never operate.
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.
The voltage of Pin No 1(orange) and 3(black) of CN-FAN.
About AC 180V over
About AC 50V over
SSR is not damaged
Check SSR
Содержание FMN0760NL
Страница 93: ... 93 Electronic Control Device 1 Indoor Unit 1 MAIN P C B ASM FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 94: ... 94 FMN1260NT FMN1860NT ...
Страница 95: ... 95 FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 96: ... 96 FMN1860NV ...
Страница 97: ... 97 2 Outdoor Unit MAIN P C B ASM FMU4480N6L ...
Страница 98: ... 98 PCB PWB ASSY SUB ...
Страница 99: ... 99 3 Display ASSY FMN1860NV FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 100: ... 100 4 SUB P W B ASSEMBLY FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 101: ... 101 Schematic Diagram 1 Indoor Unit FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 103: ... 103 FMN1260NFM B D ...
Страница 104: ... 104 FMN1860NV RY 4WAY RY OUTFAN ...
Страница 113: ... 113 354212 249951 268711 2 266010 352114 263230 352118 330870 158591 2 Cassette Type Indoor Unit FMN1260NT FMN1860NT ...
Страница 114: ... 114 346810 130411 359011 152311 135313 W0CZZ 137211 267110 352150 352150 130911 140570 268711 1 146811 ...
Страница 122: ...P No 3828A20208A August 2002 Printed in Korea ...