- 64 -
Pull the right and
the left side.
Screw
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
(1) Checking the Drainage
1) Room Type Indoor Unit
1. Remove the Grille from the cabinet
• Set the up-and-down air direction louver to
open position(horizontally) by finger pressure.
• Remove the securing screws.
• To remove the Grille, pull lower the left and
right side of the grille toward you (slightly tilted)
and lift it straight upward.
2. Check the drainage
• Pour a glass of water on the evaporator.
• Ensure if water flows drain hose of indoor unit
without any leakage.
2) Cassette Type Indoor Unit
• Drain piping must have down-slope (1/50 to 1/100):
be sure not to provide up-and-down slope to prevent
reversal flow.
• During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the
indoor unit is 32mm.
• Be sure to execute heat insulation on the drain piping.
Drain Test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump
operation:
• Connect the main drain pipe to the exterior and leave
it provisionally until the test comes to an end.
• Feed water to the flexible drain hose and check the
piping for leakage.
• Be sure to check the drain pump for normal operating
and noise when electrical wiring is complete.
• When the test is complete, connect the flexible drain
hose to the drain port on the indoor unit.
5. Checking the Drainage and Pipe forming
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
Содержание FMN0760NL
Страница 93: ... 93 Electronic Control Device 1 Indoor Unit 1 MAIN P C B ASM FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 94: ... 94 FMN1260NT FMN1860NT ...
Страница 95: ... 95 FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 96: ... 96 FMN1860NV ...
Страница 97: ... 97 2 Outdoor Unit MAIN P C B ASM FMU4480N6L ...
Страница 98: ... 98 PCB PWB ASSY SUB ...
Страница 99: ... 99 3 Display ASSY FMN1860NV FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 100: ... 100 4 SUB P W B ASSEMBLY FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 101: ... 101 Schematic Diagram 1 Indoor Unit FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 103: ... 103 FMN1260NFM B D ...
Страница 104: ... 104 FMN1860NV RY 4WAY RY OUTFAN ...
Страница 113: ... 113 354212 249951 268711 2 266010 352114 263230 352118 330870 158591 2 Cassette Type Indoor Unit FMN1260NT FMN1860NT ...
Страница 114: ... 114 346810 130411 359011 152311 135313 W0CZZ 137211 267110 352150 352150 130911 140570 268711 1 146811 ...
Страница 122: ...P No 3828A20208A August 2002 Printed in Korea ...