Defrost Control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to
cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrost control is available 45 min. later since heating mode operation started, and it will not prolong over 10 min.
• Defrost control is carried out according to the following priority order while in heating mode operation.
1st priority : Defrost control is carried out according to the indoor pipe temp 60 min. later since heating mode opera-
tion started.
2nd priority : The temp differences between the indoor pipe temp and the intake air temp 25 min. later(
∆
T1) and 45
min. later (
∆
T2) since heating mode operation started are measured, then defrost control is carried out
according to the dirrerence (
∆
T=
∆
T1-
∆
T2)
3rd priority : Defrost control is carried out according to the temp difference (E=TE1-TE2) between the indoor pipe
temperatures of 25 min later(TE1) and 45 min later (TE2) after heating mode operation started.
• When the indoor pipe temp is 41°C or above, defrost control is not carried out even if the condition is one of the
defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
More than 45 minutes
of heating operation
Within
9min. 45sec.
ON
OFF
ON
ON
ON
OFF
COMPRESSOR
4-WAY VALVE
INDOOR FAN
-6
°
C ON
12
°
C OFF
The outdoor
piping Temp.
More than 10 min.
running of compressor
More than 45 minutes
of heating operation
HOT-
START
ON
Содержание FMN0760NL
Страница 93: ... 93 Electronic Control Device 1 Indoor Unit 1 MAIN P C B ASM FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 94: ... 94 FMN1260NT FMN1860NT ...
Страница 95: ... 95 FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 96: ... 96 FMN1860NV ...
Страница 97: ... 97 2 Outdoor Unit MAIN P C B ASM FMU4480N6L ...
Страница 98: ... 98 PCB PWB ASSY SUB ...
Страница 99: ... 99 3 Display ASSY FMN1860NV FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 100: ... 100 4 SUB P W B ASSEMBLY FMN1260NFM B D TOP VIEW BOTTOM VIEW ...
Страница 101: ... 101 Schematic Diagram 1 Indoor Unit FMN0760NL FMN0960NL FMN1260NL FMN1860NL ...
Страница 103: ... 103 FMN1260NFM B D ...
Страница 104: ... 104 FMN1860NV RY 4WAY RY OUTFAN ...
Страница 113: ... 113 354212 249951 268711 2 266010 352114 263230 352118 330870 158591 2 Cassette Type Indoor Unit FMN1260NT FMN1860NT ...
Страница 114: ... 114 346810 130411 359011 152311 135313 W0CZZ 137211 267110 352150 352150 130911 140570 268711 1 146811 ...
Страница 122: ...P No 3828A20208A August 2002 Printed in Korea ...