ELECTRICAL WIRING
59
ENGLISH
Wiring of main power supply and equipment capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when
proceeding with the wiring and connections.
- The cable size is the minimum value for metal conduit wiring. The power cord size should be 1
rank thicker taking into account the line voltage drops. Make sure the power-supply voltage
does not drop more than 10%.
- Specific wiring requirements should adhere to the wiring regulations of the region.
- Power supply cords of parts of appliances for outdoor use should not be lighter than polychloro-
prene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately
from the power supply.
CAUTION
• Some installation site may require attachment of an earth leakage breaker. If no earth leakage
breaker is installed, it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or
copper wire with too large capacity may cause a malfunction of unit or fire.
!
WARNING
• Follow ordinance of your governmental organization for technical standard related to elec-
trical equipment, wiring regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no external force is imparted to
terminal connections. If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that gener-
ated overcurrent may include some amount of direct current.
!
The thickness of Minimum wire(mm
2
)
Leakage circuit
breaker(4P ELCB)
Main power wire
Branch wire
Ground wire
1Unit
2.5~6
-
2.5
Below 30~50A
100mA 0.1sec
2Unit
10~16
-
2.5
Below 75~100A
100mA 0.1sec
3Unit
25~35
-
4
Below 125~150A
100mA 0.1sec
4Unit
70
-
6
Below 175~200A
100mA 0.1sec
Ground wire
1. The power wire Between the master outdoor unit and slave1 outdoor unit – minimum : 6 mm
2
2. The power wire Between the slave1 outdoor unit and slave2 outdoor unit – minimum : 4 mm
2
3. The power wire Between the slave2 outdoor unit and slave3 outdoor unit – minimum : 2.5 mm
2
h
The above standard is CV wire standard.
h
Please use the 3-phase 4-wire quadrupole Leakage circuit breaker of circuit breaker.