PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
37
ENGLISH
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calcu-
lation purpose
• Indoor Unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit
≤
10m, equivalent length : max 13m
(for 22HP or more)
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN21
Ⓕ
: Header
Ⓖ
: Sealed piping
L 150m(200m : Conditional application)
40m(90m : Conditional application)
L 110m
40
m
Branch pipe can not be used after header
Branch pipe can not be used after header
10m or
less
H 110m
Master
Slave
Master
Slave
L 150m(200m : Conditional application)
40m(90m : Conditional application)
ODU Capacity
Master ≥ Slave
40
m
h1
Master
Slave
Combination of Y branch/header method
WARNING
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur.
!