OUTDOOR UNITS INFORMATION
9
Power Supply : 3Ø, 380V, 60Hz / 3Ø, 380 - 415V, 50Hz
Heat pump
Model Name : ARUN***LTS4
CAUTION
Notes : * We can guarantee the operation only within 130% Combination.
If you want to connect more than 130% combination, please contact us and dis-
cuss the requirement like below.
• If the operation of indoor unit is more than 130%, the airflow is operated as low in the all
indoor units.
• The number of ( ) means the number of Max. connectable indoor units, when the con-
nected capacity of indoor units is in the table above.
• The max allowable combination ratio for single LTN4 model is 160%.
Combination Ratio(50~200%)
Outdoor Number
Connection Ratio
Single outdoor units
200%
Double outdoor units
160%
Triple outdoor units
130%
!
OUTDOOR UNITS INFORMATION
ENGLISH
Number of outdoor units
1 Outdoor Unit
Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions (WxHxD)
mm
Net Weight
kg
Precharged Refrigerant amount
kg
Pipe Connctions
Liquid
mm (inch)
Gas
mm (inch)
Number of maximum connectable indoor units
8
10
12
ARUN080LTS4
ARUN100LTS4
ARUN120LTS4
ARUN080LTS4
ARUN100LTS4
ARUN120LTS4
(920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1
195 × 1
201 × 1
201 × 1
6.5
6.5
6.5
9.52 (3/8)
9.52 (3/8)
12.7 (1/2)
19.05 (3/4)
22.2 (7/8)
28.58 (1 1/8)
13(20)
16(25)
20(30)
Number of outdoor units
1 Outdoor Unit
Capacity (HP)
Model
Combination Unit
Independent Unit
Dimensions (WxHxD)
mm
Net Weight
kg
Precharged Refrigerant amount
kg
Pipe Connctions
Liquid
mm (inch)
Gas
mm (inch)
Number of maximum connectable indoor units
14
16
18
20
ARUN140LTS4
ARUN160LTS4
ARUN180LTS4
ARUN200LTS4
ARUN140LTS4
ARUN160LTS4
ARUN180LTS4
ARUN200LTS4
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1
235 × 1
235 × 1
270 × 1
280 × 1
8.5
8.5
8.5
10
12.7 (1/2)
12.7 (1/2)
15.88 (5/8)
15.88 (5/8)
28.58 (1 1/8)
28.58 (1 1/8)
28.58 (1 1/8)
28.58 (1 1/8)
23(35)
26(40)
29(45)
32(50)