PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
35
ENGLISH
Refrigerant pipe diameter from outdoor unit to first branch. (A)
* If the step up size is not available, you can not select the next higher size available.
Header Method
1 Outdoor Unit
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
2 Outdoor Units
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: Header branch
Ⓒ
: Indoor Units
Ⓓ
: Sealing
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN21
L 200m
40m
H 110m
40m
10m or
less
L 110m
L 200m
40m
Slave
Master
Slave
Master
Slave
Master
ODU Capacity
Master ≥ Slave
40m
h1
Upward Out-
door unit
total capacity
Standard Pipe Diameter
Increased Pipe Diameter
When pipe length is 90m or
more from ODU to 1st branch
When level difference is 50m
or more
HP
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
8
Ø 9.52(3/8)
Ø 19.05(3/4)
Ø 12.7(1/2)
Ø 22.2(7/8)
Ø 12.7(1/2)
not increased
10
Ø 9.52(3/8)
Ø 22.2(7/8)
Ø 12.7(1/2)
Ø 25.4(1)
Ø 12.7(1/2)
not increased
12 ~ 14
Ø 12.7(1/2)
Ø 28.58(1-1/8) Ø 15.88(5/8)
not increased
Ø 15.88(5/8)
not increased
16
Ø 12.7(1/2)
Ø 28.58(1-1/8) Ø 15.88(5/8)
Ø 31.8(1-1/4)
Ø 15.88(5/8)
not increased
18 ~ 22
Ø 15.88(5/8) Ø 28.58(1-1/8) Ø 19.05(3/4)
Ø 31.8(1-1/4)
Ø 19.05(3/4)
not increased
24
Ø 15.88(5/8)
Ø 34.9(1-3/8)
Ø 19.05(3/4)
not increased
Ø 19.05(3/4)
not increased
26 ~ 34
Ø 19.05(3/4)
Ø 34.9(1-3/8)
Ø 22.2(7/8)
Ø 38.1(1-1/2)
Ø 22.2(7/8)
not increased
36 ~ 60
Ø 19.05(3/4)
Ø 41.3(1-5/8)
Ø 22.2(7/8)
not increased
Ø 22.2(7/8)
not increased
62 ~ 64
Ø 22.2(7/8)
Ø 44.5(1-3/4)
Ø 25.4(1)
Ø 53.98(2-1/8)
Ø 25.4(1)
not increased
66 ~ 82
Ø 22.2(7/8)
Ø 53.98(2-1/8)
Ø 25.4(1)
not increased
Ø 25.4(1)
not increased