PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
3 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch(Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN31
Ⓕ
: Connection branch pipe between Outdoor
units: ARCNN21
Ⓖ
: Header
Ⓗ
: Sealing
4 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch(Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe between Outdoor
units: ARCNN41
Ⓕ
: Connection branch pipe between Outdoor
units: ARCNN31
Ⓖ
: Connection branch pipe between Outdoor
units: ARCNN21
Ⓗ
: Header
Ⓘ
: Sealing
10m or
less
H 110m
Master
Slave2
Slave1
F
E
F
E
ODU Capacity
Master ≥ Slave1 ≥ Slave2
L 150m(200m : Conditional application)
40m(90m : Conditional application)
40
m
h1
Branch pipe can not be used after header
Branch pipe can not be used after header
10m or
less
H 110m
G
F
E
G
F
E
L 150m(200m : Conditional application)
40m(90m : Conditional application)
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
40m
Master
Slave3
Slave1
Slave2
h1
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
≤
22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
< 33.6(114,700)
Ø9.52(3/8)
Ø22.2(7/8)
< 50.4(172,000)
Ø12.7(1/2)
Ø28.58(1-1/8 )
< 67.2(229,400)
Ø15.88(5/8)
Ø28.58(1-1/8 )
< 72.8(248.500)
Ø15.88(5/8)
Ø34.9(1-3/8)
< 100.8(344,000)
Ø19.05(3/4)
Ø34.9(1-3/8)
< 173.6(592,500)
Ø19.05(3/4)
Ø41.3(1-5/8)
< 184.8(630,700)
Ø22.2(7/8)
Ø44.5(1-3/4)
< 224.0(764,400)
Ø22.2(7/8)
Ø53.98(2-1/8)