- 16 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
1.3 EEV control
(1) Main EEV control
Main EEV operates with fuzzy control rules to keep the degree of super Heat(Superheat) (about 3°C)at
the evaporator outlet stable during heating mode
The degree of Superheat = Tsuction - Tevaporation
Tsuction : temperature at suction pipe sensor(°C)
Tevaporation : evaporation temperature equivalent to low pressure(°C)
(2) Subcooling EEV control(about 15°C)
Subcooling EEV works with fuzzy rules to keep the degree of Subcool at the outlet of subcooler during
cooling mode
The degree of Subcool = Tcondensation - Tliquid
Tliquid : temperature at outlet of subcooler(°C)
Tcondensation : condensation temperature equivalent to high pressure(°C)
(3) Avoiding excessive high discharge temperature : when main EEV opens some given opening and dis-
charge temperature is above 85°C in heating operation, subcooling EEV may control the "subcooling
out temperature-evaporating temperature" to be some given difference.