Troubleshooting Guide
- 74 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
501
ODU 3phase power
omission error
Error
No.
Error Type
Error Point
Main Reasons
Omitting one or more of
R,S,T input power
1. Input Voltage abnormal (R,S,T,N)
2. Check power Line connection condition
3. Inv. PCB damage
4. Inv. PCB input current sensor fault
n
Error Diagnosis and Countermeasure Flow Chart
* Measuring input voltage
* Noise filter wiring
* Field Fault Case
* R-Phase Terminal
Changed
Color.
Is input voltage normal?
No
Yes
Recheck power and installation condition
Yes
Check
R~S/S~T/T~R phase voltage is 380V±10%
R~N/S~N/T~N phase voltage is 220V±10%
→
Check connection condition and wiring if power is
abnormal
Are there any power wire
connections normal?
No
Yes
1. Check R/S/T/N wiring conditions
→
Rewire them if abnormality found.
INV. PCB LED display error
No
Replace Inv. PCB assembly.
Is Inv. PCB
normal?
No
1. Check R~N/S~N/T~N phase voltage is
220V±10%
2. Check Inv. PCB assemblywire
disconnection and wiring
→
Reassemble if abnormality found
Yes
N
T
S
R
T
S
R