Troubleshooting Guide
- 67 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
n
Error diagnosis and countermeasure flow chart
No
Yes
Is the resistance of discharge
temperature sensor normal?*
Replace discharge
temperature sensor
Is the amount of
refrigerant normal?
[refer refrigerant part]
Weld / reconnect the cracked
portion and recharge refrigerant
Is there pipe crack
or trace of leakage?
Change the amount of
refrigerant
(Charge additive amount)
Is EEV in
Compressor Module normal
at heating operation?
[refer electric
component part]
Replace Compressor Module
EEV
Does liquid injection
corresponded
operate normally?
Check liquid injection
corresponded
Is there pipe
(strainer etc.) clogging?
Check another components
and operation conditions
/ Take measures
Replace strainer
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
* Resistance value of discharge temperature sensor
10C = 362k, 25C= 200k, 50C= 82k, 100C= 18.5k
Error No.
Error Type
Error Point
Main Reasons
321
Over-increase discharge
temperature of inverter
compressor 1 at main
Compressor Module
Compressor is off because
of over-increase discharge
temperature of inverter
compressor 1
1. Temperature sensor defect of inverter
compressor 1 discharge pipe
2. Refrigerant shortage / leak
3. EEV defect
4. Liquid injection valve defect