Troubleshooting Guide
- 68 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
n
Error diagnosis and countermeasure flow chart
1. Defect of high pressure sensor
2. Defect of indoor or Compressor Module fan
3. Deformation because of damage of refrigerant pipe
4. Over-charged refrigerant
5. Defective indoor / Compressor Module EEV
6. When blocked
- Compressor Module is blocked during cooling
- Indoor unit filter is blocked during heating
7. SVC valve is clogged
8. PCB defect of Compressor Module
10. Indoor unit pipe temperature sensor defect
Error
No.
Error Type
Error Point
Main Reasons
Error happens
because of 3 times
successive
compressor off due to
over-increase of high
pressure by high
pressure sensor
Over-increase of
discharge pressure
of compressor
341
Is service valve opened ?
No
Open service valve
Are communication
cable / pipe connection
normal?
Yes
No
Is refrigerant
amount normal?
[refer refrigerant part]
Yes
No
Is fan normal?
(Indoor fan during heating
Outdoor fan during cooling)
Yes
No
Yes
Adjust refrigerant amount
Check and repair communication
cable / pipe connection
Replace related parts
(Refer to Error 105~107)
Is filter blocked
(Heating:indoor,
Cooling:outdoor
heat exchanger)?
No
Clean indoor filter (heating)
/outdoor heat exchanger (cooling)?
Is value of high pressure
sensor same as Manifold
value(Is it high actually)?
No
Replace sensor of high pressure
Yes
Yes
Check indoor unit LEV
Check indoor unit PCB
Check in/outdoor installation
condition